Ambient conditions
For the environmental limits for the safety functions and the drive, refer to the hardware
manual of your drive.
■
ACS880-07 drives, frames R6 to R11
The maximum ambient temperature for the drive with safety relays is 45 °C (113 °F). In the
temperature range +40…45 °C (+104…113 °F), the rated output current must be derated
by 2% for every added 1 °C (1.8 °F). The output current can be calculated by multiplying
the current given in the rating table by the derating factor (
k
):
T
1.00
0.90
+40 °C
+104 °F
+45 °C
+113 °F
k
0.80
Related standards and directives
Name
Standard
Safety of machinery – General principles for design – Risk assessment and risk reduction
EN ISO 12100:2010
Safety of machinery – Safety-related parts of control systems – Part 1: General principles
for design
EN ISO 13849-
1:2015
Safety of machinery – Safety-related parts of control systems – Part 2: Validation
EN ISO 13849-
2:2012
Safety of machinery – Prevention of unexpected start-up (ISO 14118:2017)
EN ISO 14118:2018
Safety of machinery – Electrical equipment of machines – Part 1: General requirements
EN 60204-1:2006 +
AC:2010
IEC 60204-1:2016
Electrical equipment for measurement, control and laboratory use - EMC requirements
- Part 3-1: Immunity requirements for safety-related systems and for equipment intended
to perform safety-related functions (functional safety) - General industrial applications
IEC 61326-3-1:2017
Functional safety of electrical/electronic/programmable electronic safety-related systems
- Part 1: General requirements
IEC 61508-1:2010
Functional safety of electrical/electronic/programmable electronic safety-related systems
- Part 2: Requirements for electrical/electronic/programmable electronic safety-related
systems
IEC 61508-2:2010
Functional safety – Safety instrumented systems for the process industry sector – Part
1: Framework, definitions, system, hardware and application programming requirements
IEC 61511-1:2016
Adjustable speed electrical power drive systems – Part 5-2: Safety requirements –
Functional
EN 61800-5-2:2007
IEC 61800-5-2:2016
Technical data 33