DC/DC converter module
■
Replacing the R8i DC/DC converter module
WARNING!
Obey the safety instructions given in
Safety instructions for ACS880
liquid-cooled multidrive cabinets and modules
(3AXD50000048633
[English]). If you ignore the safety instructions, injury or death, or damage
to the equipment can occur.
If you are not a qualified electrician, do not do installation or maintenance
work.
WARNING!
Make sure that the replacement module has exactly the same type code as the
old module.
WARNING!
Beware of hot coolant. Do not work on the liquid cooling system until the pressure
is lowered down by stopping the pumps and draining the coolant. High-pressure
warm coolant (6 bar, max. 50 °C) is present in the internal cooling circuit when it
is in operation.
WARNING!
Use the required personal protective equipment. Wear protective gloves and long
sleeves. Some parts have sharp edges.
Removing the module
1.
Repeat the steps described in section Electrical safety precautions.
2.
Remove the shrouding in front of the module.
3.
Undo the locking screws of the swing-out frame (if present) and open it.
4.
Unplug the wiring from the module and move it aside. Use cable ties to keep the wiring
out of the way.
5.
Remove the L-shaped DC busbars at the top of the module. Make note of the orientation
of the screws as well as the order of the washers.
Maintenance 85
Содержание ACS880-1604LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 1604LC DC DC converter modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 16: ...16 ...
Страница 34: ...34 ...
Страница 42: ...Kits for ACS880 1604LC R8i unit in Rittal VX25 cabinets 42 Cabinet construction ...
Страница 43: ...Stage 1 Installation of common parts Cabinet construction 43 10 ...
Страница 44: ...Stage 2 Side plates busbars and quick connectors for connecting DDC module and filter 44 Cabinet construction ...
Страница 45: ...Stage 3 Module installation parts Cabinet construction 45 10 ...
Страница 46: ...Stage 4 DDC and energy storage connection 46 Cabinet construction ...
Страница 47: ...Stage 5A DC connection with charging Cabinet construction 47 10 ...
Страница 48: ...Stage 5B DC connection without charging 48 Cabinet construction ...
Страница 49: ...Stage 6 Cooling components Cabinet construction 49 10 ...
Страница 50: ...Stage 7 DDC module and filter installation 50 Cabinet construction ...
Страница 51: ...Stage 8 Swing frame and shroud installation Cabinet construction 51 10 ...
Страница 58: ...58 ...
Страница 72: ...72 ...
Страница 124: ...124 ...
Страница 138: ...138 ...
Страница 148: ...148 ...
Страница 150: ...R8i DC DC converter module 150 Dimension drawings ...
Страница 151: ...BDCL filter module Dimension drawings 151 ...
Страница 152: ...Quick connector 152 Dimension drawings ...
Страница 153: ...BCU control unit Dimension drawings 153 ...
Страница 154: ...BAMU voltage current measurement unit Dimensions in mm 1 mm 0 0394 in 154 Dimension drawings ...
Страница 157: ...CIO 01 I O module Dimension drawings 157 ...