1. If there is double or reinforced insulation between the sensor and the live parts of the
motor: You can connect the sensor directly to the analog/digital input(s) of the drive.
See the control cable connection instructions. Make sure that the voltage does not
exceed the maximum allowed voltage over the sensor.
2. If there is basic insulation between the sensor and the live parts of the motor: You can
connect the sensor to the analog/digital input(s) of the drive. All other circuits connected
to the digital and analog inputs (typically extra-low voltage circuits) must be:
• protected against contact, and
• insulated with basic insulation from other low-voltage circuits. The insulation must be
rated for the same voltage level as the drive main circuit.
Note:
Extra-low voltage circuits (for example, 24 V DC) typically do not meet these
requirements.
Make sure that the voltage does not exceed the maximum allowed voltage over the
sensor.
As an alternative, you can connect the sensor with basic insulation to the analog/digital
input(s) of the drive, if you do not connect any other external control circuits to the drive
digital and analog inputs.
3. You can connect the sensor to the drive via an option module. The sensor and the
module must form a double or reinforced insulation between the motor live parts and
the drive control unit. See
Connecting motor temperature sensor to the drive via an
. Make sure that the voltage does not exceed the maximum
allowed voltage over the sensor.
4. You can connect a sensor to a digital input of the drive via an external relay. The sensor
and the relay must form a double or reinforced insulation between the motor live parts
and the digital input of the drive. Make sure that the voltage does not exceed the
maximum allowed voltage over the sensor.
■
Connecting motor temperature sensor to the drive via an option module
This table shows:
• option module types that you can use for the motor temperature sensor connection
• insulation or isolation level that each option module forms between its temperature sensor
connector and other connectors
• temperature sensor types that you can connect to each option module
• temperature sensor insulation requirement in order to form, together with the insulation
of the option module, a reinforced insulation between the motor live parts and the drive
control unit.
92 Guidelines for planning the electrical installation
Содержание ACS880-14
Страница 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 14: ...14...
Страница 24: ...24...
Страница 30: ...30...
Страница 54: ...54...
Страница 64: ...64...
Страница 98: ...98...
Страница 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Страница 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Страница 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Страница 150: ...150 Installation example with full cabling panels option H381...
Страница 156: ...156...
Страница 204: ...Standard configuration 204 Dimension drawings...
Страница 205: ...Location of power cable connection terminals with options H370 H356 3AXD50000038012 Dimension drawings 205...
Страница 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Страница 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Страница 208: ...LCL filter module 208 Dimension drawings...
Страница 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Страница 230: ...Declaration of conformity 230 The Safe torque off function...
Страница 236: ...Combi screw M8 30 Hex 20 N m 14 75 lbf ft Tapping screw M6 12 Torx T30 Hex 8 N m 71 lbf in 8 10 9 11 12 236...
Страница 241: ...241...
Страница 246: ...246...