NOTE: Customer wiring from T1, T2 and T3 of each sine filter to customer load must be divided
symmetrically. There must be the same quantity of equal wire size, connected to each sine filter.
(2)R11 Enclosure, Power Junction Box (+H361)
NOTE: Customer wiring from the supply to L1, L2 and L3 power blocks must be divided symmetrically. There
must be the same quantity, of equal wire size, connected to each of the 2 power blocks per phase. Power
blocks are rated for 800Amps each.
NOTE: Customer wiring from T1, T2 and T3 power blocks to customer load must be divided symmetrically.
There must be the same quantity, of equal wire size, connected to each of the 2 power blocks per phase.
Power blocks are rated for 800Amps each.
NOTE: With the customer supplied and installed harmonic filter, to maintain the 100kA SCCR rating the
harmonic filter must have a 100kA SCCR and be installed per the manufacturer’s recommendations.