Description
Term
Connection
XD24 Auxiliary voltage output, digital interlock
3)
Run enable
DIIL
DIIL
1
+24VD
DICOM
+24VD
DIOGND
2
3
4
5
+24 V DC 200 mA
4)
+24VD
Digital input ground
DICOM
+24 V DC 200 mA
+24VD
Digital input/output ground
DIOGND
XDIO Digital input/outputs
Output: Ready run
DIO1
1
DIO1
2
DIO2
Output: Running
DIO2
Ground selection
5)
J6
XDI Digital inputs
Stop (0) / Start (1)
DI1
1
DI1
DI2
DI3
DI4
DI5
DI6
2
3
4
5
6
+24VD
Forward (0) / Reverse (1)
DI2
Reset
DI3
Acc/Dec time select
6)
DI4
Constant speed 1 (1 = On)
7)
DI5
By default, not in use.
DI6
Safe torque off circuits must be closed for the drive to start.
8)
XSTO
Safety options connection
X12
Control panel connection
X13
Memory unit connection
X205
1) Current [0(4)…22 mA, R
in
= 100 ohm] or voltage [0(2)…11 V,
R
in
> 200 kohm] input selected by jumper. Change of
setting requires reboot of control unit.
2) See section
3) See section
4) Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by DIO1 and DIO2.
5) Determines whether DICOM is separated from DIOGND (ie. common reference for digital inputs floats; in practice,
selects whether the digital inputs are used in current sinking or sourcing mode). See also
. DICOM=DIOGND ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate.
6) 0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use. 1 = Acceleration/deceleration ramps
defined by parameters
23.14/23.15 in use.
7) Constant speed 1 is defined by parameter 22.26.
8) See chapter
The Safe torque off function (page 171)
.
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5
… 2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
104 Control unit of the drive
Содержание ACS880-04F-504A-3
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 36: ...36 ...
Страница 44: ...44 ...
Страница 50: ...50 Mechanical installation ...
Страница 56: ...56 ...
Страница 116: ...116 ...
Страница 122: ...4 3 2 122 Maintenance ...
Страница 128: ...128 ...
Страница 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Страница 158: ...158 ...
Страница 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Страница 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Страница 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Страница 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Страница 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Страница 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Страница 166: ...3AXD50000038119 166 Dimension drawings ...
Страница 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Страница 168: ...168 ...