![ABB ACS880-01 Series Скачать руководство пользователя страница 427](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621427.webp)
Parameters 427
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
8
DIO2
Digital input/output DIO2 (
, bit 1).
9
). -
Defines the delay time before ESP control program activates
the process control mode selected with parameter
After the drive is started during the time set in this parameter,
the automatic process control remains inactive. The pump-
motor will follow speed reference selected in parameter
0
0...30000 s
Automode start delay.
1 = 1s
Defines safe motor speed ramp setting used when automatic
process control mode is active.
In order to prevent undesired speed steps due to process
feedback signal errors or any other reason, it is
recommended to set this parameter value as high as it seems
reasonable it terms of expected speed change dynamics.
5.0
0.0...30000.0 s
Auto mode motor ramp time.
1 = 1s
Selects the source to invert process PI controller error sign.
Off
Invert process controller error sign is inactive.
Invert both
Inverts both Process1 and Process 2.
Invert Process 1
Invert process 1 control error sign.
Invert Process 2
Invert process 2 control error sign.
Process 1 control
feedback src
Defines the source for the process 1 feedback signal.
NULL
Zero
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
FBA1 ref
3
FBA2 ref
4
EFB1 ref
5
EFB2 ref
6
Estimated current
Parameter
(see page
7
Motor current %
Estimated motor current in % of nominal motor current.
8
Estimated flowrate
is used as the process feedback
source.
9
Estimated head
is used as the process feedback
source.
10
). -
Defines the value for the process 1 reference set point.
0.00
0.00...3000000.00
Process 1 control set point.
10 = 1%
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...