248 Parameters
The motor can be automatically started after a short supply
power failure using the automatic restart function. See section
(page
When this parameter is set to 0.0 seconds, automatic
restarting is disabled. Otherwise, the parameter defines the
maximum duration of the power failure after which restarting
is attempted. Note that this time also includes the DC pre-
charging delay.
WARNING!
Before you activate the function, make
sure that no dangerous situations can occur. The
function restarts the drive automatically and continues
operation after a supply break.
5.0 s
0.0 s
Automatic restarting disabled.
0
0.1 … 5.0 s
Maximum power failure duration.
1 = 1 s
Selects the motor start function for the scalar motor control
mode, ie. when
is set to
.
Notes
:
• The start function for the DTC motor control mode is
selected by parameter
.
• With permanent magnet motors,
start mode
must be used.
• This parameter cannot be changed while the drive is
running.
(page
Normal
Immediate start from zero speed.
0
Const time
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is defined by parameter
. This mode should be selected if constant
pre-magnetizing time is required (e.g. if the motor start must
be synchronized with the release of a mechanical brake).
This setting also guarantees the highest possible break-away
torque when the pre-magnetizing time is set long enough.
Note:
This mode cannot be used to start into a rotating motor.
WARNING!
The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In applications where
a full break-away torque is essential, ensure that the constant
magnetizing time is long enough to allow generation of full
magnetization and torque.
1
Automatic
This setting should be used in applications where flying starts
(ie. starting into a rotating motor) are required.
2
In a torque-controlled follower drive, forces (or selects a
source that forces) the drive to switch to speed control upon a
ramp stop (Off1 or Off3) command. This is required for an
independent ramp stop of the follower.
See also section
1 = Ramp stop forces speed control
Not selected
0.
0
Selected
1.
1
DIIL
DIIL input (
, bit 15).
2
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...