Parameters 205
Displays the status of I/O extension module 1.
No option
No module detected in the specified slot.
0
No communication
A module has been detected but cannot be communicated
with.
1
Unknown
The module type is unknown.
2
FIO-01
An FIO-01 module has been detected and is active.
15
FIO-11
An FIO-11 module has been detected and is active.
20
FAIO-01
An FAIO-01 module has been detected and is active.
24
(Visible when
)
Displays the status of the digital inputs on the extension
module. The activation/deactivation delays (if any are
specified) are ignored. A filtering time (for input mode) can be
defined by parameter
.
Bit 0 indicates the status of DI1.
Note:
The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example:
0101b = DI1 and DI3 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b
Status of digital inputs.
1 = 1
(Visible when
Displays the status of the digital input/outputs on the
extension module. The activation/deactivation delays (if any
are specified) are ignored. A filtering time (for input mode)
can be defined by parameter
Bit 0 indicates the status of DIO1.
Note:
The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example:
1001b = DIO1 and DIO4 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b
Status of digital input/outputs.
1 = 1
(Visible when
)
Displays the delayed status of the digital inputs on the
extension module. The word is updated only after
activation/deactivation delays (if any are specified).
Bit 0 indicates the status of DI1.
Note:
The number of active bits in this parameter depends on
the number of digital inputs on the extension module.
Example:
0101b = DI1 and DI3 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b
Delayed status of digital inputs.
1 = 1
(Visible when
Displays the delayed status of the digital input/outputs on the
extension module. This word is updated only after
activation/deactivation delays (if any are specified).
Bit 0 indicates the status of DIO1.
Note:
The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example:
1001b = DIO1 and DIO4 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b
Delayed status of digital input/outputs.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...