18 ACS880-01/04 +C132 marine type-approved drives
Definitions – ACS880-01
027A-7
R3
26
46
26
18.5
25
22
15
20
07A3-7
R5
8.6
12.2
8.6
5.5
7.5
5.8
3.0
4.0
09A8-7
R5
10
18
10
7.5
10
8.6
4.0
5.0
14A2-7
R5
16
22
16
11
15
10
5.5
8
018A-7
R5
21
29
21
15
20
16
11
15
022A-7
R5
26
44
26
18.5
25
21
15
20
026A-7
R5
30
54
30
22
30
26
18.5
25
035A-7
R5
39
64
39
30
40
30
22
30
042A-7
R5
49
70
49
37
50
39
30
40
049A-7
R5
49
71
49
37
50
39
30
40
061A-7
R6
59
104
59
45
60
49
37
50
084A-7
R6
73
124
73
55
75
59
45
60
098A-7
R7
94
168
94
75
100
73
55
75
119A-7
R7
119
198
119
90
125
94
75
100
142A-7
R8
137
250
137
110
150
119
90
125
174A-7
R8
171
274
171
132
200
137
110
150
210A-7
R9
230
384
230
160
250
182
132
200
271A-7
R9
257
411
257
200
250
230
160
250
3AXD00000588487
U
N
Nominal voltage of the drive. For the input voltage range, see section
Electrical
power network specification
in the hardware manual.
I
1N
Nominal rms input current
I
N
Nominal output current (available continuously with no over-loading)
P
N
Typical motor power in no-overload use
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
P
Ld
Typical motor power in light-overload use
I
max
Maximum output current. Available for 10 seconds at start. then as long as allowed
by drive temperature.
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes.
* Continuous rms output current allowing 30% overload for 1 minute every 5 minutes.
** Continuous rms output current allowing 25% overload for 1 minute every 5
minutes.
UL (NEC) RATINGS – ACS880-01 +C132
Drive
type
ACS880-
01-
Frame
size
Input
rating
Max.
cur-
rent
Output ratings
Light-overload use
Heavy-duty use
I
1N
I
max
I
Ld
P
Ld
I
Hd
P
Hd
A
A
A
kW
hp
A
kW
hp