292 Parameters
(Only visible with a BCU control unit)
Defines the drive/inverter type if it consists of parallel-
connected modules.
If the drive/inverter consists of a single module, leave the
value at
Note:
This parameter cannot be changed while the drive is
running.
Not selected
The drive/inverter does not consist of parallel-connected
modules, or type not selected.
0
[Drive/inverter type] Drive/inverter type consisting of parallel-connected modules.
-
Defines the ratio of the step-up transformer.
0.000
0.000 … 100.000
Step-up transformer ratio.
1000 = 1
96
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; data logger triggering; parameter checksum
calculation; user lock.
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under View –
Settings.)
-
Not selected
None.
0
English
English.
1033
Chinese (Simplified,
PRC)
Simplified Chinese.
2052
Pass codes can be entered into this parameter to activate
further access levels (see parameter
) or to configure the user lock.
Entering “358” toggles the parameter lock, which prevents the
changing of all other parameters through the control panel or
the Drive composer PC tool.
Entering the user pass code (by default, “10000000”) enables
parameters
, which can be used to define a
new user pass code and to select the actions that are to be
prevented.
Entering an invalid pass code will close the user lock if open,
ie. hide parameters
. After entering the code,
check that the parameters are in fact hidden. If they are not,
enter another (random) pass code.
Entering several invalid pass codes introduces a delay before
a new attempt can be made. Entering further invalid codes will
progressively lengthen the delay.
Note:
You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in a safe
place – the protection cannot be disabled even by ABB if the
code is lost.
See also section
0
0…99999999
Pass code.
-
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...