Control locations and operating modes 21
External control
When the drive is in external control, control commands are given through
• the I/O terminals (digital and analog inputs),
• the embedded fieldbus interface or an optional fieldbus adapter module
• the external (DDCS) controller interface
• the master/follower link, and/or
• the control panel.
Two external control locations, EXT1 and EXT2, are available. The user can select
the sources of the start and stop commands separately for each location by
parameters
. The operating mode can be selected separately for each
location (in parameter group
), which enables quick switching
between different operating modes, for example speed and torque control. Selection
between EXT1 and EXT2 is done via any binary source such as a digital input or
fieldbus control word (see parameter
). The source of
reference is selectable for each operating mode separately.
The control location selection is checked on a 2 ms time level.
Using the control panel as an external control source
The control panel can also be used as a source of start/stop commands and/or
reference in external control. Selections for the control panel are available in the
start/stop command source and reference source selection parameters.
Reference source selection parameters have two selections for the control panel. The
difference between the two selections is in the initial reference value after the
reference source switches to the control panel.
The panel reference is saved whenever another reference source is selected. If the
reference source selection parameter is set to
, the saved
value is used as the initial reference when control switches back to the panel. Note
that only one type of reference can be saved at a time: for example, attempting to use
the same saved reference with different operating modes (speed, torque, etc.)
causes the drive to trip on
. The panel reference can be
separately limited by parameters in group
With the reference source selection parameter set to
, the
initial panel reference value depends on whether the operating mode changes with
the reference source. If the source switches to the panel and the operating mode
does not change, the last reference from the previous source is adopted. If the
operating mode changes, the drive actual value corresponding to the new mode is
adopted as the initial value.
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...