160 Parameters
Defines the shape of the deceleration ramp at the end of the
deceleration. See parameter
.
0.000 s
0.000 …1800.000 s Ramp shape at end of deceleration.
10 = 1 s
Defines the acceleration time for the jogging function i.e. the
time required for the speed to change from zero to the speed
value defined by parameter
.
See section
60.000 s
0.000 …1800.000 s Acceleration time for jogging.
10 = 1 s
Defines the deceleration time for the jogging function i.e. the
time required for the speed to change from the speed value
defined by parameter
to zero.
See section
60.000 s
0.000 …1800.000 s Deceleration time for jogging.
10 = 1 s
In speed control mode, this parameter defines the
deceleration rate for emergency stop Off3 as the time it would
take for the speed to decrease from the value of parameter
to zero. This also applies to torque
control because the drive switches to speed control on
receiving an emergency stop Off3 command.
In frequency control mode, this parameter specifies the time it
would take for the frequency to decrease from the value of
to zero.
The emergency stop mode and activation source are selected
by parameters
respectively. Emergency stop can
also be activated through fieldbus.
Note:
Emergency stop Off1 uses the standard deceleration
torque control) or
…
3.000 s
0.000 …1800.000 s Emergency stop Off3 deceleration time.
10 = 1 s
Selects a source that forces the speed reference to zero just
before it enters the ramp function.
0 = Force speed reference to zero before the ramp function
1 = Speed reference continues towards the ramp function as
normal
Active
0.
0
Inactive
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
-
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...