126 Parameters
Selects the unit for readings and settings related to analog
input AI1.
Note:
This setting must match the corresponding hardware
setting on the drive control unit (see the hardware manual of
the drive). Control board reboot (either by cycling the power or
through parameter
) is required to
validate any changes in the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
Defines the filter time constant for analog input AI1.
Note:
The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This cannot
be changed by any parameter.
0.100 s
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
.
0.000 mA or
V
-22.000 … 22.000
mA or V
Minimum value of AI1.
1000 = 1 mA
or V
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
.
20.000 mA or
10.000 V
-22.000 … 22.000
mA or V
Maximum value of AI1.
1000 = 1 mA
or V
No.
Name/Value
Description
Def
/
FbEq16
63
%
100
T
t
O = I × (1 - e
-t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...