116 Parameters
Defines the activation delay for digital input DI5.
0.0 s
t
On
=
t
Off
=
*Electrical status of digital input. Indicated by
.
**Indicated by
0.0 … 3000.0 s
Activation delay for DI5.
10 = 1 s
Defines the deactivation delay for digital input DI5. See
parameter
0.0 s
0.0 … 3000.0 s
Deactivation delay for DI5.
10 = 1 s
Defines the activation delay for digital input DI6.
0.0 s
t
On
=
t
Off
=
*Electrical status of digital input. Indicated by
.
**Indicated by
0.0 … 3000.0 s
Activation delay for DI6.
10 = 1 s
Defines the deactivation delay for digital input DI6. See
parameter
0.0 s
0.0 … 3000.0 s
Deactivation delay for DI6.
10 = 1 s
Status of relay outputs RO8…RO1.
Example:
00000001b =
RO1 is energized, RO2…RO8 are de-energized.
-
0000h…FFFFh
Status of relay outputs.
1 = 1
Selects a drive signal to be connected to relay output RO1.
;
b2);
b1
b6);
b9)
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
(see page
2
No.
Name/Value
Description
Def
/
FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
*DI status
**Delayed DI status
Time
1
0
1
0
t
On
t
Off
t
On
t
Off
*DI status
**Delayed DI status
Time
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...