258 Parameters
99.08
Mot nom freq
Defines the nominal motor frequency.
Note:
This parameter cannot be changed while the drive is
running.
5.0 … 500.0 Hz
Nominal frequency of the motor.
10 = 1 Hz
99.09
Mot nom speed
Defines the nominal motor speed. The setting must match the
value on the rating plate of the motor.
Note:
This parameter cannot be changed while the drive is
running.
Note:
For safety reasons, after ID run, the maximum and
minimum speed limits (parameters
and
) are
automatically set to a 1.2 times bigger value than the nominal
motor speed.
0 … 10000 rpm
Nominal speed of the motor.
1 = 1 rpm
99.10
Mot nom power
Defines the nominal motor power. The setting must match the
value on the rating plate of the motor. If multiple motors are
connected to the drive, enter the total power of the motors.
The unit is selected by parameter
.
Note:
This parameter cannot be changed while the drive is
running.
0.00 … 10000.00
kW
Nominal power of the motor.
100 = 1 kW
99.11
Mot nom cosfii
Defines the cosphi of the motor for a more accurate motor
model. (Not applicable to permanent magnet motors and
synchronous reluctance motors.) Not obligatory; if set, should
match the value on the rating plate of the motor.
Note:
This parameter cannot be changed while the drive is
running.
0.00 … 1.00
Cosphi of the motor.
100 = 1
99.12
Mot nom torque
Defines the nominal motor shaft torque for a more accurate
motor model. Not obligatory.
Note:
This parameter cannot be changed while the drive is
running.
0 … 2147483.647
Nm
Nominal motor torque.
1000 = 1 N•m
No.
Name/Value
Description
FbEq
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...