Parameters 249
Warning
The drive generates an ENCODER 1/2 CABLE warning. This
is the recommended setting if the maximum pulse frequency
of sine/cosine incremental signals exceeds 100 kHz; at high
frequencies, the signals may attenuate enough to invoke the
function. The maximum pulse frequency can be calculated as
follows:
2
90.10
Enc par refresh
Setting this parameter to 1 forces a reconfiguration of the
FEN-xx interfaces, which is needed for any parameter
changes in groups 90…93 to take effect.
Note:
The parameter cannot be changed while the drive is
running.
Done
Reconfiguration done.
0
Configure
Reconfigure. The value will automatically revert to
.
1
91
91 Absol enc conf
Absolute encoder configuration. See also section
on page
91.01
Sine cosine nr
Defines the number of sine/cosine wave cycles within one
revolution.
Note:
This parameter does not need to be set when EnDat or
SSI encoders are used in continuous mode. See parameter
0…65535
Number of sine/cosine wave cycles.
1 = 1
91.02
Abs enc interf
Selects the source for the encoder absolute position.
None
Not selected.
0
Commut sig
Commutation signals.
1
EnDat
Serial interface: EnDat encoder.
2
Hiperface
Serial interface: HIPERFACE encoder.
3
SSI
Serial interface: SSI encoder.
4
Tamag. 17/33b
Serial interface: Tamagawa 17/33-bit encoder.
5
91.03
Rev count bits
Defines the number of bits used in revolution count with
multiturn encoders. Used when parameter
is set to
or
. When parameter
is set to
, setting this
parameter to a non-zero value activates multiturn data
requesting.
0…32
Number of bits used in revolution count. For example, 4096
revolutions corresponds to 12 bits.
1 = 1
91.04
Pos data bits
Defines the number of bits used within one revolution when
parameter
is set to
or
. When parameter
is set to
, this parameter is internally set to 17.
0…32
Number of bits. For example, 32768 positions per revolution
corresponds to 15 bits.
1 = 1
91.05
Refmark ena
Enables the encoder zero pulse for the absolute encoder
input (X42) of an FEN-11 module (if present). Zero pulse can
be used for position latching.
Note:
With serial interfaces (i.e. when parameter
),
zero pulse must be disabled.
No.
Name/Value
Description
FbEq
Max. pulse frequency
Pulses per rev. Max. speed in rpm
×
60
-----------------------------------------------------------------------------------------------
=
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...