Parameters 211
Dc-capacitor
Pre-selectable alarm for the drive run time counter.
4
Mot bearing
Pre-selectable alarm for the drive run time counter.
5
44.32
kWh inv lim
Sets the limit for the energy counter. The counter monitors
signal
(see page
). When the signal
reaches the limit, the alarm specified by parameter
is given.
0 … 2147483647
Alarm limit for the energy counter.
1 = 1 kWh
44.33
kWh inv alm sel
Selects the alarm for the energy counter.
Device clean
Pre-selectable alarm for the energy counter.
1
Add cool fan
Pre-selectable alarm for the energy counter.
2
Cabinet fan
Pre-selectable alarm for the energy counter.
3
Dc-capacitor
Pre-selectable alarm for the energy counter.
4
Mot bearing
Pre-selectable alarm for the energy counter.
5
45
45 Energy optimising
Energy optimization settings. See also section
45.01
Energy optim
Enables/disables energy optimization function. The function
optimizes the flux so that total energy consumption and motor
noise level are reduced when the drive operates below the
nominal load. The total efficiency (motor and drive) can be
improved by 1…10% depending on load torque and speed.
Disable
Energy optimization disabled.
0
Enable
Energy optimization enabled.
1
45.02
Energy tariff1
Price of energy per kWh. Used for reference when savings
are calculated. See parameters
,
and
0.00 …
21474836.47
Price of energy per kWh.
1 = 1
45.06
E tariff unit
Specifies the currency used for the savings calculation.
Local
The currency is determined by the setting of parameter
0
Eur
Euro.
1
Usd
US dollar.
2
45.08
Pump ref power
Motor power when connected directly to supply. Used for
reference when energy savings are calculated. See
parameters
and
.
Note:
The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value.
00.0… 1000.0%
Motor power in percent of nominal motor power.
1 = 1
45.09
Energy reset
and
Done
Reset not requested (normal operation).
0
Reset
Reset energy counters. The value reverts automatically to
.
1
No.
Name/Value
Description
FbEq
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...