Parameters 167
25
25 Critical speed
Sets up critical speeds, or ranges of speeds, that are avoided
due to, for example, mechanical resonance problems.
25.01
Crit speed sel
Enables/disables the critical speeds function.
Example:
A fan has vibrations in the range of 540 to 690 rpm
and 1380 to 1560 rpm. To make the drive to jump over the
vibration speed ranges:
• activate the critical speeds function,
• set the critical speed ranges as in the figure below.
Disable
Critical speeds are disabled.
0
Enable
Critical speeds are enabled.
1
25.02
Crit speed1 lo
Defines the low limit for critical speed range 1.
Note:
This value must be less than or equal to the value of
.
-30000 … 30000
rpm
Low limit for critical speed 1.
1 = 1 rpm
25.03
Crit speed1 hi
Defines the high limit for critical speed range 1.
Note:
This value must be greater than or equal to the value of
.
-30000 … 30000
rpm
High limit for critical speed 1.
1 = 1 rpm
25.04
Crit speed2 lo
Defines the low limit for critical speed range 2.
Note:
This value must be less than or equal to the value of
.
-30000 … 30000
rpm
Low limit for critical speed 2.
1 = 1 rpm
25.05
Crit speed2 hi
Defines the high limit for critical speed range 2.
Note:
This value must be greater than or equal to the value of
.
No.
Name/Value
Description
FbEq
540
690
1380
1560
1
Par.
2
Par.
3
Par.
4
Par.
1
2
3
4
Motor speed
(rpm)
Drive speed
(rpm)
Drive speed
(rpm)
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...