![ABB ACS850-04 series Скачать руководство пользователя страница 123](http://html1.mh-extra.com/html/abb/acs850-04-series/acs850-04-series_firmware-manual_3365228123.webp)
Parameters 123
13.19
AI4 max scale
Defines the real value that corresponds to the maximum
analogue input AI4 value defined by parameter
-32768.000 …
32768.000
Real value corresponding to maximum AI4 value.
1000 = 1
13.20
AI4 min scale
Defines the real value that corresponds to the minimum
analogue input AI4 value defined by parameter
. See the drawing at parameter
.
-32768.000 …
32768.000
Real value corresponding to minimum AI4 value.
1000 = 1
13.21
AI5 filt time
Defines the filter time constant for analogue input AI5. See
parameter
.
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
13.22
AI5 max
Defines the maximum value for analogue input AI5. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI5 maximum value.
1000 = 1 unit
13.23
AI5 min
Defines the minimum value for analogue input AI5. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI5 minimum value.
1000 = 1 unit
No.
Name/Value
Description
FbEq
AI
(scaled)
AI
(mA/V)
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...