Installation
11
Installation
What this chapter contains
This chapter instructs how to install the APBU unit into a user-defined cabinet.
Planning the installation of the APBU unit
Placement
Install the APBU unit in a heated indoor environment. Ensure the temperature meets
the requirement given in chapter
WARNING!
Avoid installing the APBU in the immediate vicinity of sources of
electromagnetic disturbance, such as relays, contactors, brake choppers and motor
cabling. The minimum recommended distance from such components is 200 mm.
Mounting and removing the APBU
The unit can be installed onto a 7.5 × 35 mm [EN50022] mounting rail (1) (2).
Remove the unit in reverse order (3) (4).
Mounting
Removal
2
3
1
4