46 Mechanical installation
Overview of the installation procedure
1. The cabinet can be installed with its back against a wall. Fasten the cabinet to the floor
with fastening clamps. For the location of the fastening clamps, see the delivery
specific dimensional drawings.
Note 1:
Leave a minimum clearance of 400 mm above the basic roof level of the cabinet
to allow the pressure release lids to open at an arc fault.
Note 2:
Leave some space at the side where the cabinet outmost hinges are to allow the
doors to open sufficiently. The doors must open 120° to allow converter module
replacement. For more accurate space requirements for the door openings, see chapter
Note 3:
Leave 115 mm free space at the right- or left-hand side of the converter for the
cooling pipe connections (depending on which side the cooling connections are).
Note 4:
Leave 150 mm free space at the right-hand side for the plug-in connectors.
Note 5:
Height adjustment can be done by using metal shims between the bottom frame
and floor.
1
150 mm (5.91 in.)
> 400 mm (15.75 in.)
Note 1: Top clearance
View from top
View from front
> 400 mm (15.75 in.)
d
Note 1: Top clearance
d = 80 mm (2.8 in.) when D150 is selected.
d = 170 mm (5.9 in.) when D150+D151 is
selected.
View from front (oD150 and
+D151)
Note 4: Right-hand clearance
View from top
Note 2: Door opening clearance
Содержание ACS800-67LC
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 22: ...22 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 52: ...52 Mechanical installation ...
Страница 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Страница 92: ...92 Maintenance 4 6 5 5 ...
Страница 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Страница 109: ...Maintenance 109 5 6 7 ...
Страница 131: ...Technical data 131 Declaration of incorporation ...
Страница 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Страница 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Страница 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Страница 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Страница 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Страница 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Страница 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Страница 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Страница 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Страница 147: ...Dimension drawings 147 Option 2H372 ...
Страница 148: ...148 Dimension drawings Option 3H372 ...
Страница 149: ...Dimension drawings 149 Option 1H373 ...
Страница 150: ...150 Dimension drawings Option 2H373 ...
Страница 151: ...Dimension drawings 151 Option 3H373 ...
Страница 152: ...152 Dimension drawings Option H375 ...