250 Parameters
Inverter
temperature
(page
23
Process PID output
(page
24
Process PID
feedback
(page
).
25
Process PID
setpoint
26
Process PID
deviation
(page
27
Source selection (see
on page
). -
Defines a filter time constant for the signal monitored by
signal supervision 1.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 1.
0.00
-21474836.00…
21474836.00
Low limit.
-
Defines the upper limit for signal supervision 1.
0.00
-21474836.00…
21474836.00
Upper limit.
-
Defines the hysteresis for the signal monitored by signal
supervision 1.
0.00
0.00…100000.00
Hysteresis.
-
Selects the mode of signal supervision function 2. Determines
how the monitored signal (see parameter
) is compared
to its lower and upper limits (
respectively).
The action to be taken when the condition is fulfilled is
selected by
Disabled
Signal supervision 2 not in use.
0
Low
Action is taken whenever the signal falls below its lower limit.
1
High
Action is taken whenever the signal rises above its upper
limit.
2
Abs low
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
3
Abs high
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
5
Abs both
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 2
exceeds its limits.
Note:
This parameter does not affect the status indicated by
.
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
Drive trips on fault
2
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 250 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...