Supplemental Installation Manual for ACS580-0P

17

ACS580-0P

Branch circuit protection

Input power is connected to the ACS580 through a door interlocked disconnect 

switch or circuit breaker. When connected to a 240V or 480V power source, the 

ACS580 with the circuit breaker option is suitable for use on a circuit capable of 

delivering not more than 100,000 RMS symmetrical amperes. When connected to a 

600V power source, F255 configurations are suitable for use on a circuit capable of 

delivering not more than 10,000 RMS symmetrical amperes (75-150 HP), and not 

more than 25,000 RMS symmetrical amperes (2-60 HP).

Fuses

Note:

 The UL listed drive fuses in the table are provided in the purchased product.

• Replacement fuses are required to be of the same class, current rating, and 

voltage rating. Fuses from other manufacturers can be used if they are 600V rated 

and meet the specifications given in the table.
• Fuses with higher current rating than specified must not be used.

575 Volt

Output Ratings

Base 

Drive 

Frame 

Size

Maximum Power Wiring Data

Type Code

1, 2

A

HP

Circuit 

Breaker 

(+F255) 

UL 

(NEMA) 

Type 1 

and 12

Circuit 

Breaker 

UL 

(NEMA) 

Type 3R

4

Disconne

ct Switch 

UL 

(NEMA) 

Type 1 

and 12

Disconne

ct Switch 

UL 

(NEMA) 

Type 3R

4

Motor 

Terminals

Ground 

Lugs UL 

(NEMA) 

Type 1 

and 12

ACS580-0P-02A7-6

2.7

2

R2

#10

62 in-lbs

#10

62 in-lbs

#10

55 in-lbs

#10

55 in-lbs

#6

1.1 ft-lbs

#2

50 in-lbs

ACS580-0P-03A9-6

3.9

3

R2

#12

62 in-lbs

#12

62 in-lbs

ACS580-0P-06A1-6

6.1

5

R2

#10

62 in-lbs

#10

62 in-lbs

ACS580-0P-09A0-6

9

7.5

R2

ACS580-0P-011A-6

11

10

R2

ACS580-0P-017A-6

17

15

R2

#6

62 in-lbs

#6

62 in-lbs

#6

55 in-lbs

#6

55 in-lbs

ACS580-0P-022A-6

22

20

R3

#2

2.6 ft-lbs

ACS580-0P-027A-6

27

25

R3

#4

62 in-lbs

#4

62 in-lbs

#4

55 in-lbs

#4

55 in-lbs

ACS580-0P-032A-6

32

30

R3

ACS580-0P-041A-6

41

40

R5

#3

62 in-lbs

Consult 

Factory

#3

55 in-lbs

Consult 

Factory

#2/0

4.1 ft-lbs

ACS580-0P-052A-6

3

52

50

R5

#2

62 in-lbs

#2

55 in-lbs

ACS580-0P-062A-6

62

60

R6

#1

62 in-lbs

#1

275 in-lbs

300 MCM

29.5 ft-lbs

ACS580-0P-077A-6

77

75

R6

#1/0

62 in-lbs

#1/0

275 in-lbs

3 x #3/0

250 in-lbs

ACS580-0P-099A-6

99

100

R7

#3/0

124 in-lbs

#3/0

275 in-lbs

500 MCM

29.5 ft.lbs

ACS580-0P-125A-6

125

125

R7

250 MCM

124 in-lbs

250 MCM

275 in-lbs

ACS580-0P-144A-6

144

150

R8

300 MCM

275 in-lbs

2 x 300 

MCM

29.6 ft-lbs

1)

“0P” represents a disconnect with fuses. 0P+F255 represents a circuit breaker.

2)

0P+F255 is rated 600Y/347V unless otherwise specified. For use on solidly grounded Wye source only.

3)

0P+F255 supports Delta network configuration. 

4)

Only available for packaged drives in box enclosures.

Содержание ACS580-0P

Страница 1: ...ACS580 0P Supplement Installation Manual for ACS580 0P ACS580 0P Enclosed Drives 230V 1 100 HP 480V 1 200 HP 575 2 150 HP ...

Страница 2: ......

Страница 3: ... safety in installation start up and maintenance 4 Electrical safety in installation start up and maintenance 5 Additional instructions for permanent magnet motor drives 7 General safety in operation 8 Cybersecurity disclaimer 8 Contents ACS580 0P Installation 10 Operation 20 Dimensions 22 ...

Страница 4: ...es R5 R9 Lift the drive with a lifting device Use the lifting eyes of the drive Frames R5 R9 Do not tip the drive over The drive is heavy and its center of gravity is high An overturning drive can cause physical injury Beware of hot surfaces Some parts such as heatsinks of power semiconductors remain hot for a while after disconnection of the electrical supply Keep the drive in its package or prot...

Страница 5: ...e and 20 07 Ext2 start trigger type in ACS580 firmware manual 3AXD50000016097 English When the control location is not set to Local text Hand is not shown on the top row of the panel and parameter 19 19 Off mode disable has value Off button disabled the stop key on the control panel will not stop the drive Frames R1 R5 Do not attempt to repair a malfunctioning drive contact your local representati...

Страница 6: ...her systems connecting the internal EMC filter will reduce the conducted emission If the drive will be connected on a corner grounded TN system make sure the EMC filter is not connected metal screws should not be installed Connections with metal screws in these systems can cause danger or damage See section Checking the compatibility with IT ungrounded and corner grounded TN systems North America ...

Страница 7: ...thing conductor or install a protective earth conductor with a cross section of at least 7 AWG 10 mm2 Cu or install a device which automatically disconnects the supply if the protective earth conductor breaks Additional instructions for permanent magnet motor drives Safety in installation start up and maintenance These are additional warnings concerning permanent magnet motor drives The other safe...

Страница 8: ...ault reset functions of the drive control program make sure that no dangerous situations can occur These functions reset the drive automatically and continue operation after a fault Note When the drive is not in the Hand mode the Off key on the control panel will not stop the drive Cybersecurity disclaimer This product is designed to be connected to and to communicate information and data via a ne...

Страница 9: ... type of your drive refer to its construction code on either Serial number label attached on upper part of the top mounting plate between the mounting holes Type code label attached to the base frame on the side of the enclosure ACS580í0Pí052Aí4 S N 2173303939 U1 3ph 400 480 VAC I2 62 52 A ACS580 0P 052A 4 Input U1 3ph 400 480 VAC I1 52 A F1 50 60 Hz U2 3ph 0 U1 I2 52 A Output Made in USA of Forei...

Страница 10: ...e enclosure can damage electrical equipment and create a hazardous condition Where parts such as conduit plates require cutting or drilling first remove the part If that is not practical cover nearby electrical components to protect them from all shavings or debris Do not connect or disconnect input or output power wiring or control wires when power is applied Never connect line voltage to drive o...

Страница 11: ...al Packaged Drive with input disconnect ACS580 0P Vertical Packaged Drive units are configured for wiring access from the bottom only The following figures show the layout and wiring connection points For drive control wiring see Maintain appropriate separation of control and power wires ...

Страница 12: ...12 Supplemental Installation Manual for ACS580 0P ACS580 0P ...

Страница 13: ...nect ACS580 Vertical Packaged Drive units are configured for wiring access from the top for UL NEMA Type 1 and 12 and from the bottom for UL NEMA Type 3R The following figures show the layout and wiring connection points For drive control wiring see Connecting the Control Cables section in the ACS580 Hardware Manual ...

Страница 14: ...14 Supplemental Installation Manual for ACS580 0P ACS580 0P ...

Страница 15: ...80 0P 024A 2 24 2 7 5 R2 6 1 1 ft lbs ACS580 0P 031A 2 30 8 10 R2 4 62 in lbs 4 62 in lbs 4 55 in lbs 4 55 in lbs ACS580 0P 046A 2 46 2 15 R3 2 62 in lbs 2 62 in lbs 2 55 in lbs 2 55 in lbs 2 2 6 ft lbs ACS580 0P 059A 2 59 4 20 R3 1 62 in lbs 1 62 in lbs 1 55 in lbs 1 55 in lbs ACS580 0P 075A 2 74 8 25 R4 1 0 62 in lbs 1 0 62 in lbs 1 0 55 in lbs 1 0 55 in lbs 1 3 0 ft lbs ACS580 0P 088A 2 88 30 R...

Страница 16: ...s ACS580 0P 027A 4 27 20 R3 8 62 in lbs 8 62 in lbs 4 55 in lbs 4 55 in lbs 2 2 6 ft lbs ACS580 0P 034A 4 34 25 R3 6 62 in lbs 6 62 in lbs 3 55 in lbs 3 55 in lbs ACS580 0P 044A 4 44 30 R3 ACS580 0P 052A 4 52 40 R4 1 0 124 in lbs 2 55 in lbs 2 55 in lbs 1 3 0 ft lbs ACS580 0P 065A 4 65 50 R4 1 0 124 in lbs 1 55 in lbs 1 55 in lbs ACS580 0P 077A 4 77 60 R4 1 0 55 in lbs 1 0 55 in lbs ACS580 0P 096A...

Страница 17: ...ype 1 and 12 Disconne ct Switch UL NEMA Type 3R4 Motor Terminals Ground Lugs UL NEMA Type 1 and 12 ACS580 0P 02A7 6 2 7 2 R2 10 62 in lbs 10 62 in lbs 10 55 in lbs 10 55 in lbs 6 1 1 ft lbs 2 50 in lbs ACS580 0P 03A9 6 3 9 3 R2 12 62 in lbs 12 62 in lbs ACS580 0P 06A1 6 6 1 5 R2 10 62 in lbs 10 62 in lbs ACS580 0P 09A0 6 9 7 5 R2 ACS580 0P 011A 6 11 10 R2 ACS580 0P 017A 6 17 15 R2 6 62 in lbs 6 62...

Страница 18: ...R8 Class T 350A Class J or RK1 400A 1 0P represents a disconnect and 0P F255 represents a circuit breaker 480 Volt Nominal Output Range Base Drive Frame Size Internal Drive Fuse Rating External Fuse for Disconnect Option Type code 1 Drive current Package power A HP Class Current rating Class Max current rating ACS580 0P 02A1 4 2 1 1 R1 Class CC 15A N A N A ACS580 0P 03A0 4 3 1 5 R1 Class CC 15A N ...

Страница 19: ...T 100A N A N A ACS580 0P 099A 6 99 100 R7 Class T 150A N A N A ACS580 0P 125A 6 125 125 R7 Class T 175A N A N A ACS580 0P 144A 6 144 150 R8 Class T 200A N A N A 1 0P represents a disconnect and 0P F255 represents a circuit breaker 2 ACS580 0P xxxx x F255 is rated 600Y 347V unless otherwise specified For use on a solidly grounded Wye source only 3 This rating when circuit breaker F255 is present su...

Страница 20: ...th a door interlocked external operating handle The operating handle can be padlocked in the OFF position padlock not supplied Enclosure options are UL NEMA Type 1UL NEMA Type 12 NEMA 1 NEMA 12 Typical power diagram Frame size Weight Standalone side by side free space Above Below Sides kg lb in mm in mm R1 35 77 7 9 200 2 0 50 R2 35 77 7 9 200 2 0 50 R3 176 79 8 7 9 200 2 0 50 R4 176 79 8 7 9 200 ...

Страница 21: ...l Installation Manual for ACS580 0P 21 ACS580 0P The following shows the front view of the ACS580 Vertical Packaged Drive configuration and identifies the major components The following is a typical power diagram ...

Страница 22: ...22 Supplemental Installation Manual for ACS580 0P ACS580 0P Dimensions Px1 1 R1 Type 1 ...

Страница 23: ...Supplemental Installation Manual for ACS580 0P 23 ACS580 0P Px1 12 R1 Type 12 ...

Страница 24: ...24 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 2 R2 Type 1 ...

Страница 25: ...Supplemental Installation Manual for ACS580 0P 25 ACS580 0P Px12 2 R2 Type 12 ...

Страница 26: ...26 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 3 R3 Type 1 ...

Страница 27: ...Supplemental Installation Manual for ACS580 0P 27 ACS580 0P Px12 3 R3 Type 12 ...

Страница 28: ...28 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 4 R4 Type 1 ...

Страница 29: ...Supplemental Installation Manual for ACS580 0P 29 ACS580 0P Px12 4 R4 Type 12 ...

Страница 30: ...30 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB3R 1 R1 R2 Type 3R ...

Страница 31: ...Supplemental Installation Manual for ACS580 0P 31 ACS580 0P PxB3R 2 R3 R4 Type 3R ...

Страница 32: ...32 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB1 3 R5 R8 Type 1 ...

Страница 33: ...Supplemental Installation Manual for ACS580 0P 33 ACS580 0P PxB12 3 R5 R8 Type 12 ...

Страница 34: ...34 Supplemental Installation Manual for ACS580 0P ACS580 0P Page intentionally left blank ...

Страница 35: ......

Страница 36: ...3AXD50000460113 REVC Effective 04 28 2022 Supersedes 12 02 2020 ABB Inc 16250 West Glendale Drive New Berlin WI 53151 USA Telephone 1 800 752 0696 Fax 1 262 785 0397 Internet www abb com drives ...

Отзывы: