Parameters 267
Abs high
Action is taken whenever the absolute value of the signal
rises above its (absolute) high limit.
4
Both
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
5
Abs both
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
Hysteresis
Action is taken whenever the signal rises above the value
defined by the high limit + 0.5 hysteresis. The action is
deactivated when the signal falls below the value defined by
the low limit - 0.5 hysteresis.
7
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note:
This parameter does not affect the status indicated by
.
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
Drive trips on fault
2
Fault if running
If running, the drive trips on fault
3
Selects the signal to be monitored by signal supervision
function 1.
Zero
None.
0
Speed
(page
).
1
Frequency
(page
3
Current
4
Torque
). 6
DC voltage
7
Output power
(page
8
AI1
(page
).
9
AI2
(page
).
10
Inverter
temperature
(page
23
Process PID output
(page
24
Process PID
feedback
(page
).
25
Process PID
setpoint
(page
).
26
Process PID
deviation
(page
).
27
). -
Defines a filter time constant for the signal monitored by
signal supervision 1.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 1.
0.00
-21474836.00…
21474836.00
Low limit.
-
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...