256 Parameters
Defines the maximum torque limit for the drive (in percent of
nominal motor torque) when
The limit is effective when
• the source selected by
is 1, or
•
and
•
is set to
See diagram at
300.0%
0.0…1600.0%
Maximum torque limit 2.
See par.
Defines the maximum allowed power fed by the inverter to the
motor in percent of nominal motor power.
300.00%
0.00…600.00%
Maximum motoring power.
1 = 1%
Defines the maximum allowed power fed by the motor to the
inverter in percent of nominal motor power.
Note:
If your application, like a pump or a fan, requires that
the motor must rotate in one direction only, use speed/
frequency limit (
) to achieve this.
Do not set parameter
to 0%, as the drive is then not able to
stop correctly.
-300.00%
-600.00…0.00%
Maximum generating power.
1 = 1%
Enables the overvoltage control of the intermediate DC link.
Fast braking of a high inertia load causes the voltage to rise
to the overvoltage control limit. To prevent the DC voltage
from exceeding the limit, the overvoltage controller
automatically decreases the braking torque.
Note:
If the drive is equipped with a brake chopper and
resistor, or a regenerative supply unit, the controller must be
disabled.
Disable
Overvoltage control disabled.
0
Enable
Overvoltage control enabled.
1
Enables the undervoltage control of the intermediate DC link.
If the DC voltage drops due to input power cut off, the
undervoltage controller will automatically decrease the motor
torque in order to keep the voltage above the lower limit. By
decreasing the motor torque, the inertia of the load will cause
regeneration back to the drive, keeping the DC link charged
and preventing an undervoltage trip until the motor coasts to
a stop. This will act as a power-loss ride-through functionality
in systems with high inertia, such as a centrifuge or a fan.
Disable
Undervoltage control disabled.
0
Enable
Undervoltage control enabled.
1
Enables/disables temperature-based output current limitation.
The limitation should only be disabled if required by the
application.
Disable
Thermal current limitation disabled.
0
Enable
Thermal current limitation enabled.
1
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...