216 Parameters
Maximum current supplied during torque boost.
100.0
15.0…300.0%
Value in percent of the nominal motor current.
1 = 1
Defines the minimum and maximum torque boost time.
If torque boost time is less than 40% of frequency
acceleration time (see parameters
), then
torque boost time is set at 40% of frequency acceleration
time.
20.0 s
0.0...60.0 s
Nominal motor time.
1 = 1%
Selects the method used to stop the drive. See also section.
Speed compensated stop is active only if
• the operation mode is not torque, and
• parameter
, or
• parameter
is
(in
case Run enable is missing).
Off
Stop according parameter
, no speed
compensated stop.
0
Speed comp FWD
If the direction of rotation is forward, speed compensation is
used for constant distance braking. Speed difference
(between used speed and maximum speed) is compensated
by running the drive with current speed before the motor is
stopped along a ramp.
If the direction of rotation is reverse, the drive is stopped
along a ramp.
1
Speed comp REV
If the direction of rotation is reverse, speed compensation is
used for constant distance braking. Speed difference
(between used speed and maximum speed) is compensated
by running the drive with current speed before the motor is
stopped along a ramp.
If the direction of rotation is forward, the drive is stopped
along a ramp.
2
Speed comp bipolar Regardless of the direction of rotation, speed compensation
is used for constant distance braking. Speed difference
(between used speed and maximum speed) is compensated
by running the drive with current speed before the motor is
stopped along a ramp.
3
This delay adds distance to the total distance traveled during
a stop from maximum speed. It is used to adjust the distance
to match requirements so that the distance traveled is not
solely determined by the deceleration rate.
0.00
0.00…1000.00 s
Speed delay.
1 = 1
This parameter sets a speed threshold below which the
Speed compensated stop feature is disabled. In this speed
region, the speed compensated stop is not attempted and the
drive stops as it would, using the ramp option.
10%
0…100%
Speed threshold as a percent of the motor nominal speed.
1 = 1%
Forces automatic restart. The parameter is applicable only
if parameter
.
Disable
Force auto restart disabled. Parameter
is in effect if its value is more than 0.0 s.
0
No.
Name/Value
Description
Def/FbEq16
Содержание ACS560
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Страница 4: ...4...
Страница 30: ...30 Start up control with I O and ID run...
Страница 32: ...32 Using the control panel...
Страница 100: ...100 Program features...
Страница 153: ...Control macros 153...
Страница 160: ...160...
Страница 374: ...374 Parameters...
Страница 408: ...408 Additional parameter data...
Страница 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Страница 504: ...504 Control chain diagrams...
Страница 508: ...508 Parameterization with drive composer...
Страница 512: ...512 Parameterization with automation builder drive manager...