ACS550-CC Packaged Drive with Bypass
Installation
Motor Overload Relay
The ACS550 with Bypass includes a Class 20 motor overload relay to provide
thermal motor protection.
Suggested Settings
Current
Set the current adjustment to the value of the full load current shown on the motor
nameplate.
Auto/Man
It is recommended the overload relay be set to the Manual Reset mode of operation.
In the Auto Reset mode, the Overload Relay contacts re-close automatically when
the bi-metals of bi-metallic versions cool or when the timer function within the
electronic versions times out. If power is applied and the switches and contacts in
the control circuit are commanding the motor to run, the motor will start as soon as
the overload relay resets.
Resetting the Overload Relay
In the event an overload relay set in the Manual Reset mode trips, it is necessary to
open the door of the enclosure and push the Reset button on the front of the
overload relay to reset it.
WARNING: If power is applied and the switches and contacts in the control
circuit are commanding the motor to run, the motor will start as soon as the
overload relay resets. Use caution when manually resetting the overload relay
to make sure it is safe to start the motor.