7.  Start up the drive

For information on the user interface, refer to the 

ACS380 User interface guide

 

(3AXD50000022224 [English]).
1.

Power up the drive.

2.

The drive software recognizes the connected adapter 
(I/O & Modbus module or some of the fieldbus 
modules) and selects the correct settings. For fieldbus 
communication refer also to 

Configure fieldbus 

communications

.

3.

Select the unit (international or US). In the 

Motor data

 

view, set the motor type: 

AsynM

: Asynchronous motor

PMSM

: Permanent magnet synchronous motor

SynMR

: Synchronous reluctance motor

4.

Set the motor control mode:

Vector

: Speed reference. This is suitable for most 

cases. The drive does an automatic standstill ID run 
when the drive is started for the first time.

Scalar

: Frequency reference. Do not use this mode 

for permanent magnet synchronous motors.
Use this mode when:
- The number of motors can change.
- The nominal motor current is less than 20% of the 
nominal drive current.

5.

Set the nominal motor values.

6.

Examine the direction of the motor.
If it is necessary, set the motor direction with the 

Phase order

 setting or with the phase order of the 

motor cable.

7.

In the 

Motor control

 view, set the start and stop mode.

8.

Set the acceleration and deceleration times.

9.

Set the maximum and minimum speeds.

10. In the 

Control macros

 view, select the applicable 

macro. To configure fieldbus communications, refer to 

Configure fieldbus 

communications

.

11. Tune the drive parameters to the application. You can use the Assistant control 

panel (ACS-AP-x) or the DriveComposer PC tool. Refer to the 

ACS380 Firmware 

manual

 (3AXD50000029275 [English]).

Configure fieldbus communications

If you have a configured variant with the preconfigured fieldbus protocol, you can 

control the drive from an external control system through the fieldbus.
When the fieldbus adapter is connected to the drive, the drive control program sets 

the applicable parameters. The preconfigured settings apply to the CANopen, 

EtherCAT, Profibus and Profinet (default in FENA-21 adapter) protocols. If you have a 

CANopen variant with the BCAN-11 adapter, refer to the exceptions in the table. In 

other fieldbus protocols (DeviceNet, Powerlink,...) refer to 

ACS380 Firmware manual

 

(3AXD50000029275 [English]) and the applicable fieldbus adapter documentation.
To configure fieldbus communications:
1.

Power up the drive.

2.

The drive software recognizes the connected fieldbus adapter and selects the 
correct fieldbus control macro.
The changed parameters which apply to all fieldbus adapters:

The parameters that apply only to specific fieldbus adapters:

3.

You can see the selected fieldbus control macro in the 

Control macros

 view or 

from parameter 96.05. In the 

Control macros view

, you can also change some 

adapter specific settings.

4.

If you need to change other parameters, you can set them manually. Refer to the 

ACS380 Firmware manual

 (3AXD50000029275 [English]) and the applicable 

fieldbus adapter documentation.

Warnings and faults generated by the drive

For the complete list of warnings and faults, refer to the 

ACS380 Firmware manual

 

(3AXD50000029275 [English]).

Ratings

IEC ratings

NEMA ratings

Fuses

For more information on fuses, circuit breakers and manual motor protectors, refer to 

the 

ACS380 Hardware manual

 (3AXD50000029274 [English]).

Dimensions and weights

Free space requirements

Ambient conditions

1) Up to 4000 m altitude is possible for 400 V units when these conditions are taken 

into account:

The maximum switching voltage for integrated Relay Output 1 is 30 V at 4000 m 
(for example, do not connect 250 V to Relay Output 1).

With the BREL-01 side option module, the maximum potential difference 
between adjacent relays is 30 V (for example, do not connect 250 V to Relay 
Output 2 and 30 V to Relay Output 3).

If the conditions are not met, the maximum installation altitude is 2000 m.

For a 3-phase 400 V drive at 2000...4000 m, only the following power systems 
are permitted: TN-S, TN-c, TN-CS, TT (not corner earthed).

Certifications

The applicable certifications are shown on the product’s type label.

Declaration of conformity

Related documents

Online list of the manuals applicable to this 

product:
Online videos related to the installation of this 

product:

https://www.youtube.com/watch?v=L-rGHZ8I1zg
https://www.youtube.com/watch?v=nICGj9ntzA0
https://www.youtube.com/watch?v=0aTWO7U2fas

Parameter 

Setting (general)

Setting (CANopen with 
BCAN-11)

20.01 Ext1 commands

Fieldbus A

Embedded fieldbus

20.03 Ext1 in1

Not selected

Not selected

20.04 Ext1 in2

Not selected

Not selected

22.11 Ext1 speed ref1

FB A ref1

EFB ref1

22.22 Constant speed sel1

Not selected

Not selected

22.23 Constant speed sel2

Not selected

Not selected

23.11 Ramp set selection

Acc/Dec time 1

Acc/Dec time 1

28.11 Ext1 frequency ref1

FB A ref1

EFB ref1

28.22 Constant frequency sel1

Not selected

Not selected

28.23 Constant frequency sel2

Not selected

Not selected

28.71 Freq. ramp set selection

Acc/Dec time 1

Acc/Dec time 1

31.11 Fault reset selection

DI2

DI1

50.01 FBA A enable

Enable

N/A

50.02 FBA A comm loss func

Fault

N/A

Parameter 

Setting

CANopen (FCAN-01-M)

51.05 Profile

CiA 402 

EtherCAT

51.02 Profile

CiA 402

Profibus

51.02 Node address

3

51.05 Profile

ABB Drives

52.01 FBA A data in1

SW 16 bit

52.02 FBA A data in2

Act1 16 bit

53.01 FBA A data out1

CW 16 bit

53.02 FBA A data out2

Ref1 16 bit

Profinet

51.02 Protocol/Profile

PNIO ABB Pro

51.04 IP configuration

Static IP

52.01 FBA A data in1

SW 16 bit

52.02 FBA A data in2

Act1 16 bit

53.01 FBA A data out1

CW 16 bit

53.02 FBA A data out2

Ref 1 16 bit

Modbus TCP/IP

51.02 Protocol/Profile

MB/TCP ABB C

Ethernet IP

51.02 Protocol/Profile

EIP ABB Pro

CANopen (BCAN-11)

58.01 Protocol enable

CANopen

Warning

Fault

Description

A2A1

2281

Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.

A2B1

2310

Overcurrent. The output current is more than the internal limit. This can be 
caused by an earth fault or phase loss.

A2B3

2330

Earth leakage. A load unbalance that is typically caused by an earth fault 
in the motor or the motor cable.

A2B4

2340

Short circuit. There is a short circuit in the motor or the motor cable.

3130

Input phase loss. The intermediate DC circuit voltage oscillates.

3181

Cross connection. The input and motor cable connections are incorrect.

A3A1

3210

DC link overvoltage. There is an overvoltage in the intermediate DC circuit.

A3A2

3220

DC link undervoltage. There is an undervoltage in the intermediate DC 
circuit.

3381

Output phase loss. All three phases are not connected to the motor.

A5A0

5091

Safe torque off. The Safe torque off (STO) function is on.

6681

EFB communication loss. Break in embedded fieldbus communication.

3

4

5

6

7

8

9

10

7510

FBA A communication. Communication lost between drive and fieldbus 
adapter.

AFF6

Identification run. The motor ID run occurs at the next start.

FA81

Safe torque off 1. The Safe torque off circuit 1 is broken.

FA82

Safe torque off 2. The Safe torque off circuit 2 is broken.

Type

ACS380-

04xx

Input 

rating

Input 

with 

choke

 Max. 

current

Output ratings

Frame

size

Nominal use

Light-duty use Heavy-duty use

I

1N

I

1N

I

max

I

N

P

N

I

Ld

P

Ld

I

Hd

P

Hd

A

A

A

A

kW

A

kW

A

kW

1-phase 

U

N

 =

 

200…240

 

V

02A4-1

5.0

4.2

3.2

2.4

0.37

2.3

0.37

1.8

0.25

R0

03A7-1

7.8

6.4

4.3

3.7

0.55

3.5

0.55

2.4

0.37

R0

04A8-1

10.1

8.3

6.7

4.8

0.75

4.6

0.75

3.7

0.55

R1

06A9-1

14.5

11.9

8.6

6.9

1.10

6.6

1.10

4.8

0.75

R1

07A8-1

16.4

13.5

12.4

7.8

1.5

7.4

1.5

6.9

1.1

R1

09A8-1

20.6

17.0

14.0

9.8

2.2

9.3

2.2

7.8

1.5

R2

12A2-1

25.6

21.1

17.6

12.2

3.0

11.6

3.0

9.8

2.2

R2

3-phase 

U

N

 =

 

200…240

 

V

02A4-2

3.8

2.4

2.2

2.4

0.37

2.3

0.37

1.2

0.25

R1

03A7-2

5.9

3.7

3.2

3.7

0.55

3.5

0.55

1.8

0.37

R1

04A8-2

7.7

4.8

6.7

4.8

0.75

4.6

0.75

3.7

0.55

R1

06A9-2

11.0

6.9

8.6

6.9

1.1

6.6

1.1

4.8

0.75

R1

07A8-2

12.5

7.8

12.4

7.8

1.5

7.4

1.5

6.9

1.1

R1

09A8-2

15.7

9.8

14.0

9.8

2.2

9.3

2.2

7.8

1.5

R1

12A2-2

19.5

12.2

17.6

12.2

3.0

11.6

3.0

9.8

2.2

R2

17A5-2

28.0

17.5

22.0

17.5

4.0

16.7

4.0

12.2

3.0

R3

25A0-2

40.0

25.0

31.5

25.0

5.5

24.2

5.5

17.5

4.0

R3

032A-2

51.2

32.0

45.0

32.0

7.5

30.8

7.5

25.0

5.5

R3

048A-2

76.8

48.0

57.6

48.0

11.0

46.2

11.0

32.0

7.5

R4

055A-2

88.0

55.0

86.4

55.0

15.0

52.8

15.0

48.0

11.0

R4

3-phase 

U

N

 = 380…480 V

01A8-4

2.9

1.8

2.2

1.8

0.55

1.7

0.55

1.2

0.37

R0

02A6-4

4.2

2.6

3.2

2.6

0.75

2.5

0.75

1.8

0.55

R1

03A3-4

5.3

3.3

4.7

3.3

1.1

3.1

1.1

2.6

0.75

R1

04A0-4

6.4

4.0

5.9

4.0

1.5

3.8

1.5

3.3

1.1

R1

05A6-4

9.0

5.6

7.2

5.6

2.2

5.3

2.2

4.0

1.5

R1

07A2-4

11.5

7.2

10.1

7.2

3.0

6.8

3.0

5.6

2.2

R1

09A4-4

15.0

9.4

13.0

9.4

4.0

8.9

4.0

7.2

3.0

R1

12A6-4

20.2

12.6

16.9

12.6

5.5

12.0

5.5

9.4

4.0

R2

17A0-4

27.2

17.0

22.7

17.0

7.5

16.2

7.5

12.6

5.5

R3

25A0-4

40.0

25.0

30.6

25.0

11.0

23.8

11.0

17.0

7.5

R3

032A-4

45.0

32.0

45.0

32.0

15.0

30.5

15.0

25.0

11.0

R4

038A-4

50.0

38.0

57.6

38.0

18.5

36.0

18.5

32.0

15.0

R4

045A-4

56.0

45.0

68.4

45.0

22.0

42.8

22.0

38.0

18.5

R4

050A-4

60.0

50.0

81.0

50.0

22.0

48.0

22.0

45.0

22.0

R4

3AXD10000299801.xls

Type
ACS380-04xx

Input 

rating

Input 

with 

choke

Output ratings

Frame

size

Nominal use

Heavy-duty use

I

1N

I

1N

I

Ld

P

Ld

I

Hd

P

Hd

A

A

A

hp

A

hp

3-phase 

U

N

 = 460 V (440…480 V)

01A8-4

2.6

1.6

1.6

0.75

1.1

0.50

R0

02A6-4

3.4

2.1

2.1

1.0

1.6

0.75

R1

03A3-4

4.8

3.0

3.0

1.5

2.1

1.0

R1

04A0-4

5.4

3.4

3.5

2.0

3.0

1.5

R1

05A6-4

7.7

4.8

4.8

2.0

3.4

2.0

R1

07A2-4

9.6

6.0

6.0

3.0

4.0

2.0

R1

09A4-4

12.2

7.6

7.6

5.0

4.8

3.0

R1

12A6-4

17.6

11.0

11.0

7.5

7.6

5.0

R2

17A0-4

22.4

14.0

14.0

10.0

11.0

7.5

R3

25A0-4

33.6

21.0

21.0

15.0

14.0

10.0

R3

032A-4

37.9

27.0

27.0

20.0

12.0

15.0

R4

038A-4

44.7

34.0

34.0

25.0

27.0

20.0

R4

045A-4

49.8

40.0

40.0

30.0

34.0

25.0

R4

050A-4

50.4

42.0

42.0

30.0

40.0

30.0

R4

3AXD10000299801.xls

Warning

Fault

Description

Symbols
H1

Height back

H2

Height back

H3

Height front

W

Width

D1

Depth 1

D2

Depth 2

M1

Mounting hole distance 1

M2

Mounting hole distance 2

Fra
me 
size

Dimensions and weights

H1

H2

H3

W

D1

D2

M1

M2

Weight

mm in mm in mm in mm

in

mm in

mm in mm in mm in kg

lb

R0 205 8.07 223 8.78 170 6.69 70 2.76 174 6.85 191 7.52 50 1.97 191 7.52 1.4 3.1
R1 205 8.07 223 8.78 170 6.69 70 2.76 174 6.85 191 7.52 50 1.97 191 7.52 1.6 3.5
R2 205 8.07 223 8.78 170 6.69 95 3.74 174 6.85 191 7.52 75 2.95 191 7.52 1.9 4.2
R3 205 8.07 223 8.78 170 6.69 169 6.65 181 7.13 191 7.52 148 5.83 191 7.52 2.9 6.4
R4 205 8.07 240 9.45 170 6.69 260 10.24 181 7.13 191 7.52 238 9.37 191 7.52 5.8 12.8

3AXD10000299801.xls

Frame size

Free space required

Above

Below

Sides

mm

in

mm

in

mm

in

R0-R4

75

2.95

75

2.95

0

0

3AXD10000299801.xls

Requirement

During operation

 (installed for stationary use)

Installation altitude

230 V units

: 0...2000 m above sea level (with derating above 1000 m)

400 V units

: 0...4000 m above sea level (with derating above 1000 m)

(1

Air temperature

-10...+50 °C (14...122 °F). Up to +60 °C with derating (except R0).
No frost allowed.

Relative humidity

Up to 95% without condensation

Contamination levels
(IEC 60721-3-3)

Class 3C2
Class 3S2

Shock (IEC 60068-2-27, 
ISTA 1A)

Not allowed

Free fall

Not allowed

CE marking

EAC marking

UL marking

TÜV Nord marking

RCM marking

Document

Code (English)

ACS380 User interface guide

3AXD50000022224 [English]

ACS380 Hardware manual

3AXD50000029274 [English]

ACS380 Firmware manual

3AXD50000029275 [English]

 3AX

D

50000

0185

53 Rev 

D EN 2018

-06-0

1

© 2018 ABB Oy. All rights reserved.