9909 MOTOR NOM
POWER
Defines the nominal motor power. Must equal the value on
the motor rating plate.
P
N
0.2…3.0 ·
P
N
kW
Power
1 =
0.1 kW /
0.1 hp
9910 ID RUN
This parameter controls a self-calibration process called the
Motor ID run. During this process, the drive operates the
motor and makes measurements to identify motor
characteristics and create a model used for internal
calculations.
OFF/IDMAGN
The Motor ID run process is not run. Identification
magnetization is performed, depending on parameter
. In identification magnetization, the
motor model is calculated at first start by magnetizing the
motor for 10 to 15 s at zero speed (motor not rotating,
except that a permanent magnet synchronous motor can
rotate a fraction of a revolution). The model is recalculated
always at start after motor parameter changes.
• Parameter
= 1 (
): Identification magnetization is performed.
= 3 (
): Identification
magnetization is not performed.
0
ON
ID run. Guarantees the best possible control accuracy. The
ID run takes about one minute. An ID run is especially
effective when:
• vector control mode is used (parameter
[
] or 2 [
]), and
• operation point is near zero speed and/or
• operation requires a torque range above the motor
nominal torque, over a wide speed range, and without
any measured speed feedback (ie, without a pulse
encoder).
Note:
The motor must be de-coupled from the driven
equipment.
Note:
Check the direction of rotation of the motor before
starting the ID run. During the run, the motor will rotate in
the forward direction.
Note:
If motor parameters are changed after ID run, repeat
the ID run.
WARNING!
The motor will run at up to approximately
50…80% of the nominal speed during the ID run.
ENSURE THAT IT IS SAFE TO RUN THE MOTOR
BEFORE PERFORMING THE ID RUN!
1
All parameters
No.
Name/Value
Description
Def/FbEq
Содержание ACS355 series
Страница 1: ...ABB machinery drives User s manual ACS355 drives ...
Страница 4: ......
Страница 16: ...16 ...
Страница 32: ...32 Operation principle and hardware description ...
Страница 58: ...58 Electrical installation ...
Страница 74: ...74 Start up control with I O and ID run ...
Страница 106: ...106 Control panels ...
Страница 120: ...120 Application macros ...
Страница 178: ...178 Program features ...
Страница 338: ...338 Fieldbus control with embedded fieldbus ...
Страница 368: ...368 Fault tracing ...
Страница 404: ...404 Dimension drawings ...
Страница 410: ...410 Appendix Resistor braking ...
Страница 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...
Страница 436: ...3AUA0000066143 Rev D EN EFFECTIVE 2018 01 01 Contact us www abb com drives www abb com drivespartners ...