Fieldbus control with embedded fieldbus
246
Drive control parameters
After the modbus communication has been set up, the drive control parameters
listed in the table below should be checked and adjusted when necessary.
The
Setting for fieldbus control
column gives the value to use when the modbus
interface is the desired source or destination for that particular signal. The
Function/
Information
column gives a description of the parameter.
Parameter
Setting for
fieldbus control
Function/Information
Modbus register
address
CONTROL COMMAND SOURCE SELECTION
ABB DRV
DCU
EXT1
COMMANDS
COMM
FB CMD WORD 1 bits 0...1 (START/
STOP) when EXT1 is selected as the active control
location.
40031
bits 0...1
EXT2
COMMANDS
COMM
FB CMD WORD 1
bits 0...1 (START/
STOP) when EXT2 is selected as the active control
location.
40031
bits 0...1
DIRECTION
FORWARD
REVERSE
REQUEST
Enables rotation direction control as defined by
parameters
1001
and
1002
. The direction control is
explained in section
. on page
.
40031
bit 2
JOGGING
SEL
COMM
Enables jogging 1 or 2 activation through
FB CMD
WORD 2 bits 20 and 21.
40032
bits 20
and 21
EXT1/
EXT2 SEL
COMM
Enables EXT1/EXT2 selection through
FB CMD
WORD 1 bit 5 (with ABB Drives profile
EFB PAR
19 bit 11).
40001
bit 11
40031
bit 5
REF1
SELECT
COMM
COMM+AI1
COMM*AI1
Fieldbus reference REF1 is used when EXT1 is
selected as the active control location. See section
on page
for information on the
alternative settings.
40002 for REF1
REF2
SELECT
COMM
COMM+AI1
COMM*AI1
Fieldbus reference REF2 is used when EXT2 is
selected as the active control location. See section
on page
for information on the
alternative settings.
40003 for REF2
OUTPUT SIGNAL SOURCE SELECTION
ABB DRV
DCU
RELAY
OUTPUT 1
COMM
COMM(-1)
Enables relay output RO control by signal
RO WORD.
40134 for signal 0134
AO1
CONTENT
SEL
135
Directs the contents of fieldbus reference
COMM
VALUE 1 to analog output AO.
40135 for signal 0135
SYSTEM CONTROL INPUTS
ABB DRV
DCU
RUN
ENABLE
COMM
Enables the control of the inverted Run Enable signal
(Run Disable) through
FB CMD WORD 1 bit 6
(with ABB drives profile
EFB PAR 19 bit 3).
40001
bit 3
40031
bit 6
FAULT
RESET SEL
COMM
Enables fault reset through fieldbus
FB CMD
WORD 1 bit 4 (with ABB drives profile
EFB PAR
19 bit 7).
40001
bit 7
40031
bit 4
LOCAL
LOCK
COMM
Local control mode lock signal through
FB CMD
WORD 1 bit 14
-
40031
bit 14
PARAM
SAVE
DONE; SAVE
Saves parameter value changes (including those made
through fieldbus control) to permanent memory.
41607
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......