Actual signals and parameters
225
52 PANEL COMM
Communication settings for the control panel port on the drive
5201
STATION ID
Defines the address of the drive. Two units with the same address are not
allowed on-line.
1
1…247
Address
1 = 1
5202
BAUD RATE
Defines the transfer rate of the link.
9.6
9.6 kbit/s
9.6 kbit/s
1 = 0.1 kbit/s
19.2 kbit/s
19.2 kbit/s
38.4 kbit/s
38.4 kbit/s
57.6 kbit/s
57.6 kbit/s
115.2 kbit/s
115.2 kbit/s
5203
PARITY
Defines the use of parity and stop bit(s). The same setting must be used in all
on-line stations.
8 NONE 1
8 NONE 1
No parity bit, one stop bit
0
8 NONE 2
No parity bit, two stop bits
1
8 EVEN 1
Even parity indication bit, one stop bit
2
8 ODD 1
Odd parity indication bit, one stop bit
3
5204
OK MESSAGES
Number of valid messages received by the drive. During normal operation,
this number increases constantly.
0
0…65535
Number of messages
1 = 1
5205
PARITY ERRORS
Number of characters with a parity error received from the Modbus link. If the
number is high, check that the parity settings of the devices connected on the
bus are the same.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of characters
1 = 1
5206
FRAME ERRORS
Number of characters with a framing error received by the Modbus link. If the
number is high, check that the communication speed settings of the devices
connected on the bus are the same.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of characters
1 = 1
5207
BUFFER OVERRUNS Number of characters which overflow the buffer, i.e. number of characters
which exceed the maximum message length, 128 bytes.
0
0…65535
Number of characters
1 = 1
5208
CRC ERRORS
Number of messages with an CRC (cyclic redundancy check) error received
by the drive. If the number is high, check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of messages
1 = 1
53 EFB PROTOCOL
Embedded fieldbus link settings. See chapter
5302
EFB STATION ID
Defines the address of the device. Two units with the same address are not
allowed on-line.
1
0...247
Address
1 = 1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......