Actual signals and parameters
220
4024
PID SLEEP DELAY
Defines the delay for the sleep start function. See parameter
PID
SLEEP LEVEL. When the motor speed falls below the sleep level, the
counter starts. When the motor speed exceeds the sleep level, the counter is
reset.
60
0.0…3600.0 s
Sleep start delay
1 = 0.1 s
4025
WAKE-UP DEV
Defines the wake-up deviation for the sleep function. The drive wakes up if
the process actual value deviation from the PID reference value exceeds the
set wake-up deviation (
4025
) longer than the wake-up delay (
). Wake-up
ERROR VALUE INV settings.
If parameter 4005 is set 0:
Wake-up level = PID reference (4010) - Wake-up deviation (4025).
If parameter 4005 is set to 1:
Wake-up level = PID reference (4010) + Wake-up deviation (4025)
PID SLEEP LEVEL.
0
x…x
Unit and range depend on the unit and scale defined by parameters
WAKE-UP DELAY and
UNIT SCALE.
4026
WAKE-UP DELAY
Defines the wake-up delay for the sleep function. See parameter
PID
SLEEP LEVEL.
0.5
0.00…60.00 s
Wake-up delay
1 = 0.01 s
4027
PID 1 PARAM SET
Defines the source from which the drive reads the signal that selects
between PID parameter set 1 and 2.
PID parameter set 1 is defined by parameters
…
PID parameter set 2 is defined by parameters
…
SET1
SET 1
PID SET 1 is active.
0
DI1
Digital input DI1. 1 = PID SET 2, 0 = PID SET 1.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
SET 2
PID SET 2 is active.
7
TIMED FUNC 1
Timed PID SET 1/2 control. Timed function 1 inactive = PID SET 1, timed
function 1 active = PID SET 2. See parameter group
.
8
TIMED FUNC 2
See selection TIMED FUNC 1.
9
TIMED FUNC 3
See selection TIMED FUNC 1.
10
TIMED FUNC 4
See selection TIMED FUNC 1.
11
DI1(INV)
Inverted digital input DI1. 0 = PID SET 2, 1 = PID SET 1.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
4025
PID reference
4025
t
Wake-up level when 4005 = 1
Wake-up level when 4005 = 0
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......