Actual signals and parameters
143
Actual signals
No.
Name/Value
Description
FbEq
01 OPERATING DATA
Basic signals for monitoring the drive (read-only)
0101
SPEED & DIR
Calculated motor speed in rpm. A negative value indicates reverse
direction.
1 = 1 rpm
0102
SPEED
Calculated motor speed in rpm
1 = 1 rpm
0103 OUTPUT FREQ
Calculated drive output frequency in Hz. (Shown by default on the panel
Output mode display.)
1 = 0.1 Hz
0104
CURRENT
Measured motor current in A. (Shown by default on the panel Output
mode display.)
1 = 0.1 A
0105
TORQUE
Calculated motor torque in percent of the motor nominal torque
1 = 0.1%
0106
POWER
Measured motor power in kW
1 = 0.1 kW
0107
DC BUS VOLTAGE
Measured intermediate circuit voltage in VDC
1 = 1 V
0109
OUTPUT VOLTAGE
Calculated motor voltage in VAC
1 = 1 V
0110
DRIVE TEMP
Measured IGBT temperature in °C
1 = 0.1°C
0111
EXTERNAL REF 1
External reference REF1 in rpm or Hz. Unit depends on parameter
MOTOR CTRL MODE setting.
1 = 0.1 Hz /
1 rpm
0112
EXTERNAL REF 2
External reference REF2 in percent. Depending on the use, 100% equals
the maximum motor speed, nominal motor torque, or maximum process
reference.
1 = 0.1%
0113
CTRL LOCATION
Active control location. (0) LOCAL; (1) EXT1; (2) EXT2. See section
on page
1 = 1
0114
RUN TIME (R)
Elapsed drive running time counter (hours). The counter can be reset by
pressing the UP and DOWN buttons simultaneously when the control
panel is in Parameter mode.
1 = 1 h
0115
KWH COUNTER (R)
kWh counter. The counter can be reset by pressing UP and DOWN
buttons simultaneously when the control panel is in Parameter mode.
1 = 1 kWh
0120
AI1
Relative value of analog input AI1 in percent
1 = 0.1%
0121
AI2
Relative value of analog input AI2 in percent
1 = 0.1%
0124
AO1
Value of analog output AO in mA
1 = 0.1 mA
0126
PID 1 OUTPUT
Output value of the process PID1 controller in percent
1 = 0.1%
0127
PID 2 OUTPUT
Output value of the PID2 controller in percent
1 = 0.1%
0128
PID 1 SETPNT
Setpoint signal (reference) for the process PID1 controller. Unit depends
on parameter
UNIT,
UNIT SCALE and
PID 1 PARAM
SET settings.
-
0129
PID 2 SETPNT
Setpoint signal (reference) for the PID2 controller. Unit depends on
parameter
UNIT and
UNIT SCALE settings.
-
0130
PID 1 FBK
Feedback signal for the process PID1 controller. Unit depends on
parameter
UNIT,
UNIT SCALE and
PID 1 PARAM SET
settings.
-
0131
PID 2 FBK
Feedback signal for the PID2 controller. Unit depends on parameter
UNIT and
UNIT SCALE settings.
-
0132
PID 1 DEVIATION
Deviation of the process PID1 controller, i.e. the difference between the
reference value and the actual value. Unit depends on parameter
UNIT,
UNIT SCALE and
PID 1 PARAM SET settings.
-
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......