240 Actual signals and parameters
4027
PID 1 PARAM SET
-5…11
1
0
Defines how selections are made between PID set 1 and PID set 2.
PID parameter set selection. When set 1 is selected, parameters
are
used.
When set 2 is selected, parameters
are used.
0 = SET 1 – PID set 1 (parameters
) is active.
1 = DI1 – Defines digital input 1 as the control for PID set selection.
• Activating the digital input selects PID set 2.
• De-activating the digital input selects PID set 1.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as the control for PID set selection.
• See DI1 above.
7 = SET 2 – PID set 2 (parameters 4101…4126) is active.
8…11 = TIMER 1…4 – Defines the Timer as the control for the PID set selection (Timer
de-activated = PID set 1; Timer activated = PID set 2)
.
-1 = DI1(INV) – Defines an inverted digital input 1 as the control for PID set selection.
• Activating the digital input selects PID set 1.
• De-activating the digital input selects PID set 2.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as the control
for PID set selection.
• See DI1(INV) above.
4028
PID OUT MIN
-1000.0 … 1000.0%
1 = 0.1%
-100.0%
Defines the minimum value of PID output.
4029
PID OUT MAX
-1000.0 … 1000.0%
1 = 0.1%
-100.0%
Defines the maximum value of PID output.
4030
SLEEP BOOST TIME
0.0 … 3600.0 s
1 = 0.1 s
0.0 s
Defines the boost time for the sleep boost step. See parameter
4031
SLEEP BOOST
STEP
0.0 … 100.0%
1 = 0.1%
0.0%
When the drive is entering sleep mode, the reference (PID setpoint) is increased by
this percentage for the time defined by parameter
4032
PID REF ACC TIME
0.0 … 1800.0 s
1 = 0.1 s
0.0 s
Defines the time for the reference (PID setpoint) increase from 0 to 100%.
Note:
Parameters
are active even if the process PID set 2 (
) is used. Acceleration time
Group 40: Process PID set 1
Code
Description
Range
Resolution
Default
S
Referenc
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...