Group 16: System controls
This group defines a variety of system level locks, resets and enables.
1503
AO1 CONTENT MAX
Depends on selection
-
60.0
Sets the maximum content value
• Content is the parameter selected by parameter
• Maximum value refers to the maximum content value that will be converted to an
analog output.
1504
MINIMUM AO1
0.0 … 20.0 mA
0.1 mA
4.0 mA
Sets the minimum output current.
1505
MAXIMUM AO1
0.0 … 20.0 mA
0.1 mA
20.0 mA
Sets the maximum output current.
1506
FILTER AO1
0 … 10 s
0.1 s
0.1 s
Defines the filter time constant for AO1.
• The filtered signal reaches 63% of a step change within the time specified.
• See the figure in parameter
.
Group 16: System controls
Code
Description
Range
Resolution
Default
S
1601
RUN ENABLE
-5…7
1
0
Selects the source of the run enable signal.
0 = NOT SEL – Allows the drive to start without an external run enable signal.
1 = DI1 – Defines digital input DI1 as the run enable signal.
• This digital input must be activated for run enable.
• If the voltage drops and de-activates this digital input, the drive will coast to stop
and not start until the run enable signal resumes.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as the run enable signal.
• See DI1 above.
7 = COMM – Assigns the fieldbus Command word as the source for the run enable
signal.
• Bit 6 of the Command word 1 (parameter
) activates the
run disable signal.
• See fieldbus user’s manual for detailed instructions.
-1 = DI1(INV) – Defines an inverted digital input 1 as the run enable signal.
• This digital input must be de-activated for run enable.
• If this digital input activates, the drive will coast to stop and not start until the run
enable signal resumes.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as the run
enable signal.
• See DI1(INV) above.
Group 15: Analogue outputs
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...