164 Actual signals and parameters
1103
REF1 SELECT
0...32
1
1
Selects the signal source for external reference REF1.
0 = KEYPAD – Defines the control panel as the reference source.
1 = AI1 – Defines analog input 1 (AI1) as the reference source.
2 = AI2 – Defines analog input 2 (AI2) as the reference source.
3 = AI1/JOYST – Defines analog input 1 (AI1), configured for joystick operation, as the
reference source.
• The minimum input signal runs the drive at the maximum reference in the reverse
direction. Define the minimum using parameter
.
• The maximum input signal runs the drive at maximum reference in the forward
direction. Define the maximum using parameter
.
= 3 (request).
WARNING!
Because the low end of the reference range commands full reverse
operation, do not use 0 V as the lower end of the reference range. Doing so
means that if the control signal is lost (which is a 0 V input) the result is full reverse
operation. Instead, use the following set-up so that loss of the analog input triggers a
fault, stopping the drive:
(
) at 20% (2 V or 4 mA).
to a value 5% or higher.
to 1 (FAULT).
Group 11: Reference select
Code
Description
Range
Resolution
Default
S
+2 %
-2 %
10 V /
H
YSTERESIS
4 %
OF
F
ULL
S
CALE
EXT
REF
1
MIN
-
EXT
REF
1
MIN
-
EXT
REF
1
MAX
EXT
REF
1
MIN
EXT
REF
1
MAX
-
EXT
REF
1
MIN
2 V / 4
M
A
0 V / 0
M
A
20
M
A
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...