52 Electrical installation
Default I/O connection diagram
The default connection of the control signals depends on the application macro in
use, which is selected with parameter
The default macro is the ABB standard macro. It provides a general purpose I/O
configuration with three constant speeds. Parameter values are the default values
given in section
Default values with different macros
on page
. For information on
other macros, see chapter
on page
The default I/O connections for the ABB standard macro are given in the figure below.
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency reference
: 0…10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Not in use by default. 0…10 V
6
GND
Analog input circuit common
7
AO
Output frequency value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
Forward (0) / Reverse (1)
14 DI3
Constant speed selection
1)
15 DI4
Constant speed selection
1)
16 DI5
Acceleration and deceleration selection
2)
X1B
17 ROCOM
Relay output 1
No fault [Fault (-1)]
18 RONC
19 RONO
20 DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21 DOOUT
22 DOGND
max. 500 ohm
1…10 kohm
3)
1)
See parameter group
:
2)
0 = ramp times according to parameters
.
1 = ramp times according to parameters
.
3)
360 degree grounding under a clamp.
Tightening torque: 0.4 N·m (3.5 lbf·in).
DI3 DI4 Operation (parameter)
0
0
Set speed through AI1
1
0
Speed 1 (
0
1
Speed 2 (
1
1
Speed 3 (