350 Technical data
Control connection data
Analog inputs X1A: 2
and 5
Voltage signal,
unipolar
0 (2)…10 V,
R
in
> 312 kohm
bipolar
-10…10 V,
R
in
> 312 kohm
Current signal,
unipolar
0 (4)…20 mA,
R
in
= 100 ohm
bipolar
-20…20 mA,
R
in
= 100 ohm
Potentiometer reference
value (X1A: 4)
10 V ± 1%, max. 10 mA,
R
< 10 kohm
Resolution
0.1%
Accuracy
±1%
Analog output X1A: 7
0 (4)…20 mA, load < 500 ohm
Auxiliary voltage X1A: 9
24 V DC ± 10%, max. 200 mA
Digital inputs X1A:
12…16
(frequency input X1A:
16)
Voltage
12…24 V DC with internal or external
supply
Type
PNP and NPN
Frequency input
Pulse train 0…16 kHz (X1A: 16 only)
Input impedance
2.4 kohm
Relay output X1B:
17…19
Type
NO + NC
Max. switching voltage
250 V AC / 30 V DC
Max. switching current
0.5 A / 30 V DC; 5 A / 230 V AC
Max. continuous current
2 A rms
Digital output X1B:
20…21
Type
Transistor output PNP
Max. switching voltage
30 V DC
Max. switching current
100 mA / 30 V DC, short-circuit
protected
Frequency
10 Hz …16 kHz
Resolution
1 Hz
Accuracy
0.2%
EIA-485 interface X1C:
23…26
Cable
Shielded twisted pair, impedance
100…150 ohm
Termination
Daisy-chained bus, without drop lines
Isolation
Bus interface isolated from the drive
Transfer rate
1.2…76.8 kbit/s
Communication type
Serial, asynchronous, half duplex
Protocol
Modbus
Clearance and creepage distance
The clearance and creepage distance between I/O connections and
mains circuit is 5.5 mm, which guarantees safety insulation of
overvoltage category 3 (IEC 60664-1).
Efficiency
Approximately 95 to 98% at nominal power level, depending on the
drive size and options
Degrees of protection
IP20 (cabinet installation) / UL open: Standard enclosure. The drive
must be installed in a cabinet to fulfil the requirements for shielding
from contact.
IP20 / NEMA 1: Achieved with an option kit including a hood and a
connection box.