![ABB ACS310 Скачать руководство пользователя страница 327](http://html.mh-extra.com/html/abb/acs310/acs310_user-manual_2963327.webp)
Fault tracing 327
Embedded fieldbus faults
Embedded fieldbus faults can be traced by monitoring group
parameters. See also fault/alarm
.
No master device
If there is no master device on line, parameter
and
values remain unchanged.
What to do:
• Check that the network master is connected and properly configured.
• Check the cable connection.
Same device address
If two or more devices have the same address, parameter
value increases with every read/write command.
What to do:
• Check the device addresses. No two devices on line may have the same address.
Incorrect wiring
If the communication wires are swapped (terminal A on one device is connected to
terminal B on another device), parameter
S value remains
unchanged and parameter
increases.
What to do:
• Check the EIA-485/RS-232 interface connection.
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182