260 Actual signals and parameters
5303 EFB BAUD
RATE
Defines the transfer rate of the link.
9.6 kbit/s
1.2 kbit/s
1.2 kbit/s
1 =
0.1 kbit/s
2.4 kbit/s
2.4 kbit/s
4.8 kbit/s
4.8 kbit/s
9.6 kbit/s
9.6 kbit/s
19.2 kbit/s
19.2 kbit/s
38.4 kbit/s
38.4 kbit/s
57.6 kbit/s
57.6 kbit/s
76.8 kbit/s
76.8 kbit/s
5304 EFB PARITY
Defines the use of parity and stop bit(s) and the data length.
The same setting must be used in all on-line stations.
8 NONE 1
No parity bit, one stop bit, 8 data bits
0
8 NONE 2
No parity bit, two stop bits, 8 data bits
1
8 EVEN 1
Even parity indication bit, one stop bit, 8 data bits
2
8 ODD 1
Odd parity indication bit, one stop bit, 8 data bits
3
5305 EFB CTRL
PROFILE
Selects the communication profile. See section
on page
ABB DRV LIM
ABB drives limited profile
0
DCU PROFILE DCU profile
1
ABB DRV
FULL
ABB drives profile
2
5306 EFB OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
0…65535
Number of messages
1 = 1
5307 EFB CRC
ERRORS
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of messages
1 = 1
5308 EFB UART
ERRORS
Number of messages with a character error received by the
drive
0
0…65535
Number of messages
1 = 1
5309 EFB STATUS
Status of the EFB protocol
IDLE
EFB protocol is configured, but not receiving any messages. 0
EXECUT INIT
EFB protocol is initializing.
1
TIME OUT
A time out has occurred in the communication between the
network master and the EFB protocol.
2
CONFIG
ERROR
EFB protocol has a configuration error.
3
OFF-LINE
EFB protocol is receiving messages that are NOT
addressed to this drive.
4
ON-LINE
EFB protocol is receiving messages that are addressed to
this drive.
5
All parameters
No.
Name/Value
Description
Def/FbEq