Actual signals and parameters 283
8127 MOTORS
Sets the actual number of PFC controlled motors (maximum
7 motors: 1 speed regulated, 3 connected direct-on-line and
3 spare motors).
This value includes also the speed regulated motor.
This value must be compatible with the number of relays
allocated to PFC if the Autochange function is used.
If Autochange function is not used, the speed regulated
motor does not need to have a relay output allocated to PFC
but it needs to be included in this value.
2
1…7
Number of PFC motors
1 = 1
8128 AUX START
ORDER
Sets the start order of the auxiliary motors.
EVEN
RUNTIME
Time sharing is active. Evens out the cumulative run time of
the auxiliary motors. The start order depends on the run
times: The auxiliary motor whose cumulative run time is
shortest is started first, then the motor whose cumulative
run time is the second shortest etc. When the demand
drops, the first motor to be stopped is the one whose
cumulative run time is longest.
1
RELAY
ORDER
The start order is fixed to be the order of the relays.
2
98 OPTIONS
External serial communication activation
9802 COMM PROT
SEL
Activates the external serial communication and selects the
interface.
Note:
Before activating embedded fieldbus communication,
to LONG VIEW
(3).
NOT SEL
No communication
0
STD MODBUS Embedded fieldbus, EIA-485 interface (I/O terminals
Fieldbus control with the embedded
1
MODBUS
RS232
Embedded fieldbus. Interface: RS-232 (ie control panel
on page
.
10
99 START-UP DATA
Language selection. Definition of motor set-up data.
9901 LANGUAGE
Selects the display language used on the Assistant control
panel.
Note:
With the ACS-CP-D Assistant control panel, the
following languages are available: English (0), Chinese (1),
Korean (2) and Japanese (3).
ENGLISH
British English
0
ENGLISH (AM) American English
1
DEUTSCH
German
2
ITALIANO
Italian
3
ESPAÑOL
Spanish
4
PORTUGUES
Portuguese
5
NEDERLANDS Dutch
6
FRANÇAIS
French
7
DANSK
Danish
8
All parameters
No.
Name/Value
Description
Def/FbEq
Aotewell Ltd
www.aotewell.com