258 Actual signals and parameters
SUPRV1
OVER
Trigger on
(parameter
). See parameter group
.
12
DRIVE START Trigger when the drive receives a start command
13
TIMER TRIG
Pump cleaning sequence is started periodically at intervals
14
DI1(INV)
Trigger on the falling edge of digital input DI1
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
DI1(INV)S1O
Enable on the falling edge of digital input DI1, trigger on
(parameter
). See
parameter group
.
-7
DI2(INV)S1O
See selection
.
-8
DI3(INV)S1O
See selection
.
-9
DI4(INV)S1O
See selection
.
-10
DI5(INV)S1O
See selection
.
-11
4602 FWD STEP
Defines the forward step frequency for the pump cleaning
sequence in percent of the nominal motor frequency
0.0%
0.0…100.0%
Forward step frequency
1 = 0.1%
4603 REV STEP
Defines the reverse step frequency for the pump cleaning
sequence in percent of the nominal motor frequency
0.0%
0.0…100.0%
Reverse step frequency
1 = 0.1%
4604 OFF TIME
Defines the length of the interval between forward and
reverse steps in the pump cleaning sequence in seconds.
0.0 s
0.0…1000.0 s
Off time (step interval)
1 = 0.1 s
4605 FWD TIME
Defines the duration of each forward step in the pump
cleaning sequence in seconds.
0.0 s
0.0…1000.0 s
Forward step duration
1 = 0.1 s
4606 REV TIME
Defines the duration of each reverse step in the pump
cleaning sequence in seconds.
0.0 s
0.0…1000.0 s
Reverse step duration
1 = 0.1 s
4607 TRIG TIME
Defines the time for setting
of parameter
0.0 h
0.0…200.0 h
Trigger time in hours
1 = 0.1 h
4608 COUNT
Number of steps to be performed in the pump cleaning
sequence.
0
0…100
Number of steps
1 = 1
52 PANEL COMM
Communication settings for the control panel port on the
drive
5201 STATION ID
Defines the address of the drive. Two units with the same
address are not allowed on-line.
1
1…247
Address
1 = 1
All parameters
No.
Name/Value
Description
Def/FbEq