Actual signals and parameters 255
4419 PROFILE
OUTP LIM
Supervision limit for the Application profile protection
100.0%
-500.0…500.0% Supervision limit
1 = 0.1%
4420 PROF LIMIT
ON DLY
Delay time for the Application profile protection
0.00 h
0.00…100.00 h Delay time
1 = 0.01 h
4421 PIPEFILL
ENABLE
Enables the Precharge function, which calculates reference
steps.
NOT SEL
Not enabled
0
DI1
When DI1 is active (1), Precharge is active when the drive is
started. If DI1 becomes inactive (0) before Precharge is
finished, normal PID control is enabled.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
ACTIVE
Precharge is active at every start-up.
7
DI1(INV)
When DI1 is inactive (0), Precharge is active when the drive
is started. If DI1 becomes active (1) before Precharge is
finished, normal PID control is enabled.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
4422 PIPEFILL
STEP
Defines the speed step used in Precharge. The PID
reference ramp time is specified by parameter
.
The speed step is added to the reference after the time
has
elapsed and the change in feedback defined by parameter
has not been reached.
0.0%
0.0…100.0%
Speed step in percent of the maximum speed output
1 = 0.1%
4423 REQ ACT
CHANGE
Defines the requested change in process feedback during
the time that is set by parameter
.
If the requested change in the feedback is not reached,
is added to the speed reference.
0.0%
0.0…100.0%
Value in percent of the maximum speed
1 = 0.1%
4424 ACT CHANGE
DELAY
Defines the time that is waited after the feedback value is
compared with the old feedback value.
If parameter
is measured in the
feedback value, the speed reference stays as it is. If
is not seen in the feedback value, the value
of parameter
reference.
0.0 s
0.1…6000.0 s
Delay time
1 = 0.1 s
All parameters
No.
Name/Value
Description
Def/FbEq