240 Actual signals and parameters
ACT1-ACT2
Subtraction of ACT1 and ACT2
2
ACT1+ACT2
Addition of ACT1 and ACT2
3
ACT1*ACT2
Multiplication of ACT1 and ACT2
4
ACT1/ACT2
Division of ACT1 and ACT2
5
MIN(ACT1,2)
Selects the smaller of ACT1 and ACT2
6
MAX(ACT1,2)
Selects the higher of ACT1 and ACT2
7
sqrt(ACT1-2)
Square root of the subtraction of ACT1 and ACT2
8
sqA1+sqA2
Addition of the square root of ACT1 and the square root of
ACT2
9
sqrt(ACT1)
Square root of ACT1
10
COMM FBK 1
value
11
COMM FBK 2
value
12
AVE(ACT1,2)
Average of ACT1 and ACT2
13
4015 FBK
MULTIPLIER
Defines an extra multiplier for the value defined by
. Parameter is used mainly in
applications where feedback value is calculated from
another variable (eg flow from pressure difference).
0.000
-32.768…
32.767
Multiplier. If parameter value is set to zero, no multiplier is
used.
1 = 0.001
4016 ACT1 INPUT
Defines the source for actual value 1 (ACT1). See also
AI1
Uses analog input 1 for ACT1
1
AI2
Uses analog input 2 for ACT1
2
CURRENT
Uses current for ACT1
3
TORQUE
Uses torque for ACT1
4
POWER
Uses power for ACT1
5
COMM ACT 1
Uses value of signal
for ACT1
6
COMM ACT 2
Uses value of signal
for ACT1
7
FREQ INPUT
Frequency input
8
4017 ACT2 INPUT
Defines the source for actual value ACT2. See also
.
All parameters
No.
Name/Value
Description
Def/FbEq