210 Actual signals and parameters
ON (LOAD)
Switching frequency can adapt to loading instead of limiting
the output current. This allows maximum loading with all
switching frequency selections. The drive automatically
decreases the actual switching frequency if loading is too
high for the selected switching frequency.
2
2608 SLIP COMP
RATIO
Defines the slip gain for the motor slip compensation
control. 100% means full slip compensation, 0% means no
slip compensation. Other values can be used if a static
speed error is detected despite the full slip compensation.
Example:
35 Hz constant speed reference is given to the
drive. Despite the full slip compensation (
= 100%), a manual tachometer measurement from
the motor axis gives a speed value of 34 Hz. The static
speed error is 35 Hz - 34 Hz = 1 Hz. To compensate the
error, the slip gain should be increased.
0%
0…200%
Slip gain
1 = 1%
2609 NOISE
SMOOTHING
Enables the noise smoothing function. Noise smoothing
distributes the acoustic motor noise over a range of
frequencies instead of a single tonal frequency resulting in
lower peak noise intensity. A random component with an
average of 0 Hz is added to the switching frequency set by
.
Note:
Parameter has no effect if parameter
is set to 16 kHz.
DISABLE
Disabled
0
ENABLE
Enabled
1
2610 USER
DEFINED U1
Defines the first voltage point of the custom U/f curve at the
frequency defined by parameter
.
See section
.
19% of
U
N
0…120% of
U
N
V Voltage
1 = 1 V
2611 USER
DEFINED F1
Defines the first frequency point of the custom U/f curve.
10.0 Hz
0.0…500.0 Hz Frequency
1 = 0.1 Hz
2612 USER
DEFINED U2
Defines the second voltage point of the custom U/f curve at
the frequency defined by parameter
. See section
on page
38% of
U
N
0…120% of
U
N
V Voltage
1 = 1 V
2613 USER
DEFINED F2
Defines the second frequency point of the custom U/f curve. 20.0 Hz
0.0…500.0 Hz
Frequency
1 = 0.1 Hz
2614 USER
DEFINED U3
Defines the third voltage point of the custom U/f curve at the
frequency defined by parameter
.
See section
.
47.5% of
U
N
0…120% of
U
N
V Voltage
1 = 1 V
2615 USER
DEFINED F3
Defines the third frequency point of the custom U/f curve.
25.0 Hz
0.0…500.0 Hz
Frequency
1 = 0.1 Hz
2616 USER
DEFINED U4
Defines the fourth voltage point of the custom U/f curve at
the frequency defined by parameter
. See section
on page
76% of
U
N
All parameters
No.
Name/Value
Description
Def/FbEq