Application macros 111
SPFC control macro
This macro provides parameter settings for pump and fan control (SPFC) applications
with a soft start function. To enable the macro, set the value of parameter
to 15 (
).
For the parameter default values, see section
Default values with different macros
on
page
. If you use other than the default connections presented below, see section
Note:
Parameter
must remain in the default setting 0 (
).
Default I/O connections
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Ext. ref. 1 (Hand) / Ext. ref. 2 (PID/PFC)
: 0…10 V
1)
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Process actual value
: 4…20 mA
3)
6
GND
Analog input circuit common
7
AO
Output frequency value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1) (Hand)
13 DI2
Hand (0) / PID/PFC (1) control selection
14 DI3
Interlock:
Deactivation always stops the drive
15 DI4
Interlock:
Deactivation stops constant speed motor
16 DI5
Stop (0) / Start (1) (PID/PFC)
X1B
17 ROCOM
Relay output 1
PFC
18 RONC
19 RONO
20 DOSRC
Digital output, max. 100 mA
PFC
21 DOOUT
22 DOGND
1…10 kohm
2)
1)
Hand:
0…10 V -> 0…50 Hz.
PID/PFC: 0…10 V -> 0…100% PID setpoint.
2)
360 degree grounding under a clamp.
3)
The signal source must be powered
externally. See the manufacturer’s
instructions. An example of a connection
using a two-wire sensor is given on page
.
Tightening torque: 0.4 N·m (3.5 lbf·in).