Start-up and control with I/O   21

• motor nominal voltage (parameter 

9905

)

Setting of parameter 

9905

 is shown below as an 

example of parameter setting with the Basic Control 
Panel. You find more detailed instructions in chapter

 

Control panels, 

section 

Basic Control Panel 

in 

ACS310 

User’s Manual

 (3AUA0000044201 [English]).

 

1. To go to the Main menu, press 

 if the bottom 

line shows OUTPUT; otherwise press 

 

repeatedly until you see MENU at the bottom.

 

2. Press keys 

/

 until you see “PAr”, and 

press 

.

 

3. Find the appropriate parameter group with keys 

/

 and press 

.

 

4. Find the appropriate parameter in the group with 

keys 

/

.

 

5. Press and hold 

 for about two seconds until the 

parameter value is shown with 

 under the value.

 

6. Change the value with keys 

/

. The value 

changes faster while you keep the key pressed 
down.

 

7. Save the parameter value by pressing 

.

 

Enter the rest of the motor data:

• motor nominal current (parameter 

9906

)

Allowed range: 0.2…2.0 ·

 I

2N

A

 

• motor nominal frequency (parameter 

9907

)

 

• motor nominal speed (parameter 

9908

)

 

• motor nominal power (parameter 

9909

)

 

Select the application macro (parameter 

9902

according to how the control cables are 
connected. The default value 1 (

ABB 

STANDARD

) is suitable in most cases.

 

REM

PAR

FWD

9905

 

REM

MENU

FWD

rEF

 

REM

PAR

FWD

-01-

 

REM

PAR

FWD

9901

 

REM

PAR

FWD

9905

 

SET

V

REM

PAR

SET

FWD

400

V

REM

PAR

SET

FWD

380

REM

PAR

FWD

9905

 

REM

PAR

FWD

9906

 

REM

PAR

FWD

9907

 

REM

PAR

FWD

9908

 

REM

PAR

FWD

9909

 

REM

PAR

FWD

9902

 

Содержание ACS310

Страница 1: ...Short Form User s Manual ACS310 Safety Table of contents Mechanical installation Electrical installation Start up and control with I O...

Страница 2: ...00044200 2 ACS310 User s Manual 3AUA0000044201 OPTION MANUALS Code EN MFDT 01 FlashDrop User s Manual 3AFE68591074 2 MREL 01 Relay Output Extension Module User s Manual for ACS310 ACS350 3AUA000003597...

Страница 3: ...TN systems 13 Connecting the power cables 14 Connecting the control cables 16 Installation checklist 18 5 Start up and control with I O How to start up the drive 19 How to control the drive through t...

Страница 4: ...4 Table of contents Providing feedback on ABB Drives manuals 39 Document library on the Internet 39...

Страница 5: ...the drive is switched off Do not make any insulation or voltage withstand tests on the drive Disconnect the internal EMC filter when installing the drive on an IT system an ungrounded power system or...

Страница 6: ...drive The drive can be adjusted to operate the motor at speeds above and below the speed provided by connecting the motor directly to the power line Do not activate automatic fault reset functions if...

Страница 7: ...C max 10 mA AI2 Analog input 2 GND AI1 Analog input 1 0 10 V SCR Screen Analog output 0 20 mA L1 3 phase power supply 200 480 V AC U2 V2 W2 AC motor M 3 EMC VAR EMC filter grounding screw Varistor gro...

Страница 8: ...ted 60 Hz frequency Configuration J404 ACS CP C Basic Control Panel 1 J400 ACS CP A Assistant Control Panel 1 R700 ACS310 User s Manual in English 3AUA0000044201 EN R701 ACS310 User s Manual in German...

Страница 9: ...space is required on the sides so drives can be mounted immediately next to each other Note Make sure that dust from drilling does not enter the drive during the installation With screws 1 Mark the ho...

Страница 10: ...allation 3 Position the drive onto the screws on the wall 4 Tighten the screws in the wall securely On DIN rail 1 Click the drive to the rail To detach the drive press the release lever on top of the...

Страница 11: ...11 Fasten clamping plates 1 Fasten the clamping plate to the plate at the bottom of the drive with the provided screws 2 For frame sizes R0 R2 fasten the I O clamping plate to the clamping plate with...

Страница 12: ...12 Mechanical installation...

Страница 13: ...nternal EMC filter when installing the drive on an IT system an ungrounded power system or a high resistance grounded over 30 ohms power system otherwise the system will be connected to ground potenti...

Страница 14: ...ical installation section Selecting the power cables in ACS310 User s Manual 3AUA0000044201 English Note Do not use an asymmetrically constructed motor cable If there is a symmetrically constructed gr...

Страница 15: ...me sizes R0 R2 1 7 N m 15 lbf in for R3 and 2 5 N m 22 lbf in for R4 2 Strip the motor cable and twist the shield to form as short a pigtail as possible Fasten the twisted shield under the grounding c...

Страница 16: ...V 3 GND Analog input circuit common 4 10V Reference voltage 10 V DC max 10 mA 5 AI2 Not in use by default 0 10 V 6 GND Analog input circuit common 7 AO Output frequency value 0 20 mA 8 GND Analog outp...

Страница 17: ...cables twist also the grounding conductors of each pair in the cable together and connect the bundle to the SCR terminal terminal 1 5 Analog signals Strip the outer insulation of the analog signal cab...

Страница 18: ...motor and drive as well as Technical data Motor connection data in ACS310 User s Manual 3AUA0000044201 English ELECTRICAL INSTALLATION See Electrical installation on page 13 and Planning the electrica...

Страница 19: ...rs To be able to view them set parameter 1611 PARAMETER VIEW to 3 LONG VIEW Check the installation See the checklist in section Installation checklist on page 18 How you start up the drive depends on...

Страница 20: ...oes not support languages See parameter 9901 for the values of the available language alternatives For instructions on how to set parameters with the Assistant Control Panel see chapter Control panels...

Страница 21: ...old for about two seconds until the parameter value is shown with under the value 6 Change the value with keys The value changes faster while you keep the key pressed down 7 Save the parameter value b...

Страница 22: ...parameter 1611 PARAMETER VIEW to 3 LONG VIEW Invert the phases by changing the value of parameter 9914 to the opposite ie from 0 NO to 1 YES or vice versa Verify your work by applying input power and...

Страница 23: ...t up assistant is stopped STARTING THE GUIDED SET UP The Start up assistant now guides you through the set up tasks starting with the motor set up Set the motor data to exactly the same value as on th...

Страница 24: ...y Press to start the motor Check that the actual direction of the motor is the same as indicated on the display means forward and reverse Press to stop the motor To change the direction of the motor r...

Страница 25: ...nd control with I O 25 FINAL CHECK After the whole set up is completed check that there are no faults or alarms shown on the display and the panel LED is green and does not blink The drive is now read...

Страница 26: ...witch between remote and local control In remote control the panel display shows text REM STARTING AND CONTROLLING THE SPEED OF THE MOTOR Start by switching digital input DI1 on Basic Control Panel Te...

Страница 27: ...2008 MAXIMUM FREQ see page 31 is set from an external control system an integer value of 1 corresponds to 0 1 Hz All the read and sent values are limited to 16 bits 32768 32767 Term Definition Actual...

Страница 28: ...F1 SELECT AI1 AI1 AI1 DI3U 4D NC AI1 AI1 AI1 AI1 1106 REF2 SELECT AI2 AI2 AI2 AI2 AI2 PID1OUT PID1OUT PID1OUT 1201 CONST SPEED SEL DI3 4 DI4 5 DI3 4 DI5 NOT SEL DI3 NOT SEL NOT SEL 1304 MINIMUM AI2 1...

Страница 29: ...aximum value in Hz See the example for parameter 1104 REF1 MIN in ACS310 User s Manual 3AUA0000044201 English 1 0 1 Hz 12 CONSTANT SPEEDS Constant speed drive output frequency selection and values By...

Страница 30: ...function Run enable signal on no fault supply voltage within acceptable range and emergency stop signal off 1 RUN Running Start signal on Run enable signal on no active fault 2 FAULT 1 Inverted fault...

Страница 31: ...ating limits Actual acceleration time depends on parameter 2204 RAMP SHAPE 1 setting 5 0 s 0 0 1800 0 s Time 1 0 1 s 2203 DECELER TIME 1 Defines the deceleration time 1 ie the time required for the sp...

Страница 32: ...digital signal speed control applications 4 HAND AUTO Hand Auto macro to be used when two control devices are connected to the drive Device 1 communicates through the interface defined by external co...

Страница 33: ...e The drive cannot supply the motor with a voltage greater than the input power voltage Note that the output voltage is not limited by the nominal motor voltage but increased linearly up to the value...

Страница 34: ...Must be equal to the value on the motor rating plate Type dependent 50 18000 rpm Speed 1 1 rpm 9909 MOTOR NOM POWER Defines the nominal motor power Must equal the value on the motor rating plate PN 0...

Страница 35: ...5 2 4 2 6 4 2 0 75 1 R1 03x 03A6 4 6 6 3 3 3 6 5 8 1 1 1 5 R1 03x 04A5 4 7 6 4 1 4 5 7 2 1 5 2 R1 03x 06A2 4 10 6 5 6 6 2 9 8 2 2 3 R1 03x 08A0 4 12 8 7 3 8 0 12 8 3 3 R1 03x 09A7 4 15 0 8 8 9 7 15 4...

Страница 36: ...ad Note 2 The ratings apply at ambient temperature of 40 C 104 F for I2N and 50 C 122 F for ILD In multimotor systems the output current of the drive must be equal to or greater than the calculated su...

Страница 37: ...03x 19A4 2 25 35 6 0 10 6 10 6 0 10 03x 26A8 2 63 60 10 0 8 10 8 10 0 8 03x 34A1 2 80 80 16 0 6 16 6 16 0 6 03x 50A8 2 100 100 25 0 2 25 2 16 0 4 3 phase UN 380 480 V 380 400 415 440 460 480 V 03x 01...

Страница 38: ...fic limits Input cable fuses For installation in the United States branch circuit protection must be provided in accordance with the National Electrical Code NEC and any applicable local codes To fulf...

Страница 39: ...ct training For information on ABB product training navigate to www abb com drives and select Training courses Providing feedback on ABB Drives manuals Your comments on our manuals are welcome Go to w...

Страница 40: ...c Automation Technologies Drives Motors 16250 West Glendale Drive New Berlin WI 53151 USA Telephone 262 785 3200 800 HELP 365 Fax 262 780 5135 ABB Beijing Drive Systems Co Ltd No 1 Block D A 10 Jiuxia...

Отзывы: