196 Parameters
If parameter
is set
to 0%, this parameter defines the maximum time an
emergency stop (mode Off1 or Off3) is allowed to
take. If the motor has not stopped when the time
elapses, the drive trips on
, and
coasts to a stop.
If
is set to a value other than 0%, this parameter
defines a delay between the receipt of the emergency
stop command and the activation of the supervision.
It is recommended to specify a short delay to allow
the speed change rate to stabilize.
0 s
0…100 s
Maximum ramp-down time, or supervision activation
delay.
1 = 1 s
Selects the warnings to be suppressed. This
parameter is a 16-bit word with each bit
corresponding to a warning. Whenever a bit is set to
1, the corresponding warning is not logged to event
log.
0000h
0000h…FFFFh
Word for disabling warnings.
1 = 1
Selects the stop mode when a non-critical fault
occurs.
Coast
Coast
The drive coasts to stop.
0
Emergency ramp
The drive follows the ramp specified for an
emergency stop by parameter
.
1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Reserved
1
DC link undervoltage
1 = Warning
is suppressed.
2…4
Reserved
5
Emergency stop off2
1 = Warning
is suppressed.
4
Emergency stop off1, off3 1 = Warning
is
suppressed.
7…15
Reserved
Reserved
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...