194 Parameters
Stall speed limit in rpm. See parameter
150.00 rpm
0.00…10000.00 rpm
Stall speed limit.
See par.
Stall frequency limit. See parameter
Note:
Setting the limit below 10 Hz is not
recommended.
15.00 Hz
0.00…1000.00 Hz
Stall frequency limit.
See par.
Stall time. See parameter
.
20 s
0…3600 s
Stall time.
-
Defines, together with
and
, the maximum allowed speed
of the motor (overspeed protection). If the speed
) exceeds the speed limit
defined by parameter
or
by more than the
value of this parameter, the drive trips on the
fault.
WARNING!
This function only supervises the
speed in vector motor control mode. The
function is not effective in scalar motor control
mode.
Example:
If the maximum speed is 1420 rpm and
speed trip margin is 300 rpm, the drive trips at
1720 rpm.
500.00 rpm
0.00…10000.00 rpm
Overspeed trip margin.
See par.
No.
Name/Value
Description
Default
FbEq 16
Speed (
Time
Overspeed trip level
Overspeed trip level
0