346 Fault tracing
0011
Program too large.
Remove blocks until the error stops.
0012
Program is empty.
Correct the program and download it to
the drive.
001C
A non-existing parameter or
block is used in the parameter.
Edit the program to correct the parameter
reference, or use an existing block.
001E
Output to parameter failed
because the parameter was
write-protected.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
0023
Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
0024
Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
Other
-
Contact your local ABB representative,
quoting the auxiliary code.
64B2
User set fault
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
. Retry.
6681
EFB comm loss
Programmable fault:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the EIA-485
terminals 25, 26, 27 and 28 on the
control unit.
6682
EFB config file
Embedded fieldbus (EFB)
configuration file could not be
read.
Contact your local ABB representative.
6683
EFB invalid
parameterization
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Check the settings in parameter group
6684
EFB load fault
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Contact your local ABB representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6685
EFB fault 2
Fault reserved for the EFB
protocol application.
Check the documentation of the protocol.
6686
EFB fault 3
Fault reserved for the EFB
protocol application.
Check the documentation of the protocol.
Code
(hex)
Fault / Aux. code
Cause
What to do